User guide
Table Of Contents

MR-2100/2200 Programming Manual
19
Interpreting Flashing LED’s
The LEDs have the following meaning when flashing:
Message Receive is a group of a radio buttons for setting which panels this annunciator will display
messages for. If all panels are chosen, every message in the system is displayed. If custom is selected,
then all messages from the listed panels will be displayed.
Common LED is located directly below the Hot LED setting. This is the LED zone the annunciator will use
for common alarm, supervisory and trouble indication. It is a summation of the zone LEDs of the
annunciator. Any LED zone may be used. The zone chosen will not be available for general annunciation.
Entering a zone of 0 will disable the common zone.
Ports is located below the Common LED setting. It is not displayed for MR-2914 Annunciators. This option
enables (double) or disables (single) the COM 1 network port. If both ports are enabled, the Next ID text
box will become available (see above for a description of Next ID).
2.7 Outputs Dialog
Overview
The Outputs Dialog (see Figure 11) allows for the programming of the panel’s outputs and function
relays.
Figure 11: Panel Outputs
Zone n alarm: Acknowledge available Zone n+2 alarm: 2nd Stage Inhibit available
Zone n supervisory: Reset available (green) Zone n+2 supervisory Future use
Zone n trouble: Reset available (yellow) Zone n+2 trouble Future use
Zone n+1 alarm: Signal Silence active Zone n+3 alarm Future use
Zone n+1 supervisory: Signal Silence
available
Zone n+3 supervisory Future use
Zone n+1 trouble: 2nd Stage Inhibit active Zone n+3 trouble Power On
Note: The Power On LED refers to the 24 VDC to the annunciator, not to any AC source.