User manual
Security & Electronic Technologies GmbH Seite 9
Startup
After the contents indicator has been installed, it can be started up. Before
programming, you need to ascertain the tank data and enter the values into
the right column Input value of the following table. Then, enter the values for
the individual entry steps. Optionally, the device can also be programmed as
explained in the enclosed Quick Guide.
Setting a
parameter:
Press ENTER to call the setup mode.
Select the desired setting parameter via PLUS. Press
ENTER to call up the value selection for the parameter.
Set the value with PLUS/MINUS, press ENTER to save.
Quitting the
setup mode:
You can quit the setup mode at any time.
Select 8. Exit and press ENTER to go back to the
standard display mode.
Step
Input function
Input value
1. Probe
Select probe measuring range (see type
label of the probe) - default value is
250 mbar
______mbar
2. Fluid
(medium)
Select the medium, e.g.:
- heating oil (default): Heat.oil
- Diesel: Diesel
- select other stored media with + / - or
enter density value ...kg/m3
For unknown density values, see the
Notes on Programming
__________
3. Tank
(tank shape)
Select the tank shape, e.g.:
- linear (default): Linear
- cylindrical horizontal: Cyl.
- cyl. horizontal 50 to 100 m³:Cyl.>50m3
__________
4. Volume
(tank volume)
Enter tank volume (or maximum fill
level):e. g.: 20.000L
Important: Please see a volume table for
the highest value, if available.
For a 100 m³ cyl. buried tank, this may for
example be the value 100 600 litres.
_________L