User manual
Page 18 Security & Electronic Technologies GmbH
Technical specification
Indicator
Pursuant to EN 50081-1,
EN 50082-1, EN 61010-1 / A2
Supply voltage: 230 V AC 50 Hz
Degree of protection: IP 30 or
IP 65 acc. to IEC 529
Power input: max. 2 VA
Measuring input: 4 – 20 mA;
U0 = 20 V
Resolution: 10 Bit
Accuracy: ± 1 %
Relay output:
Switching voltage: max. 250 V AC
Switching current: max. 3.5 A
Optional (see accessories)
Analogue output: 0 - 5 V DC
4-20 mA
Dimensions W x H x D in [mm]:
120 x 120 x 49 (IP30) or
130 x 130 x 60 (IP65)
Housing: Polystyrene (IP30)
or
Polycarbonate (IP65)
Probe element (relative pressure probe for level detection)
Operating voltage: 20 V DC
Degree of protection: IP 68 acc. to
IEC529
Material: V4A ; POM;FPM; HD-PE
Length of probe (without cable)
90 mm
Standard version: 250 mbar
Length of probe connection
cable 6 m
Installation position: vertically suspended, or horizontally supine
Temperature range: Ambience operating media: 0 °C to 80 °C