User manual
Page 12 Security & Electronic Technologies GmbH
Wall thickness of inner casing 2 cm reduce value for inner height by
approx. 4 cm, reduce volume for 10 m³ by 5%, for 20 m³ by 4%, for 50 m³ by
3% and for 100 m³ by 2.5%.
Example 3 Well, 7.50 m maximum water level from ground of the well
(fill level 4.20 m), relay switching function is desired.
Probe TDS-6029 (measuring range 0 – 1000 mbar), indication in m water
column.
Step Entries
1. Probe 1000 mbar 1000mbar
2. Medium: water H2O
3. Tank shape (well): linear Linear
4. Volume 7500l
(indicated in m) 7500L (set with +/- keys)
5. Inner tank height 7.50m 750 cm (set with +/- keys)
6. Relay1 – ON at <05% -
OFF at >10% active On: 05% Off:10%
7. Relay2 – no function
8. Exit press PLUS key to go to
12. Unit – indicated unit: m Unit: m
13. Rounding: auto auto (just confirm with ENTER)
14. Exit press ENTER to see the indication e.g. 4.20m
Notes on programming
Menu
item
Setting
Description
0. Exit
Back to display mode
1.
Probe
100mbar
150mbar
250mbar
500mbar
1000mbar
2000mbar
3000mbar
5000mbar
Set mbar
Cal mode
Tank height heating oil up to 1.2 m – water up to 1 m
Tank height heating oil up to 1.8 m – water up to 1.5 m
Standard probe - tank height heating oil up to 3 m –
water up to 2.5 m
Tank height heating oil up to 6 m – water up to 5 m
Tank height heating oil up to 12 m – water up to 10 m
Tank height heating oil up to 24 m – water up to 20 m
Tank height heating oil up to 36 m – water up to 30 m
Tank height heating oil up to 60 m – water up to 50 m
Entry of a specific probe with different measuring
range Is only indicated if item 10. Set h or 11. Set V
has been activated