User manual

Security & Electronic Technologies GmbH Seite 11
Examples for programming
Example 1 Basement tank for 6000 litres heating oil, litre indication,
linear steel tank
Inner height 165 cm, (fill level 125 cm)
Standard probe TDS-6023 0 250 mbar
Step Entries/selection
1. Probe 250 mbar 250mbar
2. Medium: heating oil Heat.oil
3. Tank shape: linear Linear
4. Tank volume: 6000 litres 6000L (set with +/- keys)
5. Inner tank height: 165 cm 1.650mm (set with +/- keys)
6. Relay 1 no function deactive
7. Relay 2 no function deactive
8. Exit press ENTER to see the indication e.g. 4550L
Example 2 Buried tank, cylindrical, horizontal, for 100.600 litres Diesel oil
Inner height 2.886 m, (fill level 54 cm)
Standard probe TDS-6023 0 250 mbar
Step Entries
1. Probe 250 mbar 250mbar
2. Medium: Diesel Diesel
3. Tank shape cyl. horiz. >50m³ Cyl. >50m3
4. Tank volume: 100.600 l 100600L (exact value from volume table)
5. Inner tank height: 288.6 cm 2886 (exact value from volume table)
6. Relay 1 no function inactive
7. Relay 2 - no function inactive
8. Exit press ENTER to see the indication e.g. 12.800L
Tank with inner casing
For tanks with inner casing (e.g. cyl. horizontal or basement-welded tanks),
the entries for inner height and volume should be adjusted.
Examples:
Wall thickness of inner casing 0.5 cm reduce value for inner height by
approx. 1 cm, reduce volume for 10 m³ by 1.3%, for 20 m³ by 1%, for 50 m³
by 0.8% and for 100 m³ by 0.7%.