User manual
Page 10 Security & Electronic Technologies GmbH
5. Height
(tank height
or max. filling
height)
Enter inner tank height in mm: e. g.:
2.500 mm (max. value = 9.999 mm)
(height without dome)
Important: Please see a volume table for
the highest value, if available.
For a 100 m³ cyl. buried tank, this may be
f. e. the value 288 cm = 2.880 mm.
Steps 6 + 7 are only required for SmartBox 2 and SmartBox 3
SmartBox 2:
6. Relay1
or
SmartBox 3:
6. Beeper
(acoustic
alarm
transmitter)
Enter relay switch points as percentage
from 01 to 99 (and/or as °C value from
-99 to +99) – only for a probe with
temperature measuring function)
deactive activate with + / - to
active press Enter to confirm
On: 10% ON: set with + / - Enter
Off: 12% OFF: set with + / - Enter
On: +0°C ON: set with + / - Enter
Off: +0°C OFF: set with + / - Enter
Deactivate the relay and the beeper via
deactive or input of 0% or 0°C (both for
On and Off).
On ___%
Off ___%
On ___°C
Off ___°C
7. Relay2
See 6. Relay 1 for the data for Relay 2
8. Exit (quit)
Press Enter to return to display mode
After performing entry steps 1 - 7, the programming process is completed.
After confirmation of step 8 “Exit“, the device automatically returns to
standard display mode; the current tank contents is shown in the display.
Special functions are available under entry steps 9 to 13 (see later).
After the end of setup, do not forget to re-screw the housing cover!