Instructions
P. 8
Setup and Operation
Version 04-2017
Example 3 Fountain, 7.50 m max. water level from ground (present level 4.20 m)
Probe TDS-6131 (measuring range 0-1000 mbar), display in m of water level.
Device RELAY. Relay 1 has to protect the pump against running dry (switch off):
Menu item
1. Measuring probe
2. Liquid
3. Tank shape
4. Tank volume
5. Tank height
5b. Fillspace
6. View
7. Relay 1
Relay 2
8. ( Exit )
. . .
12. Unit
13. Rounding
14. Exit [Enter]
Input
1000 mbar
Water
Linear
(Volume) Alternatively max. level 7.50 m
7500 [ ] (enter by +/- )
(Max.level) 750.0 cm (enter by +/- )
99%=7.50m
View details: Percent + Level
Active => ‘On’ at 99 % ; ‘Off’ at 10 % of the level.
Deactive
Jump to the next step by pressing [+]
Set display unit to ‘m’.
Automatically (default).
Displaying mode => ... e.g. ‘ 4.20 m 56 %’
Tank with interior mantle
In case of tank with interior mantle (e.g. horizontal cylindric or cellar steel tank) correct
the input values.
Example: Mantle thickness ~ 0.5 cm to 1 cm
=> Reduce ’5. Interior height’ by ~ 2 cm
=> Reduce ‘4. Volume’: Volume up to 10 m³ => reduce volume by 3.0%
Volume up to 20 m³ => reduce volume by 2.5%
Volume up to 50 m³ => reduce volume by 2.0%
Volume up to 100 m³ => reduce volume by 1.5%