Instructions
Version 04-2017
Setup and Operation
P. 7
In case of RELAY also setup the switching points for relay 2.
RELAY
8. Exit
Press [Enter] to leave the setup mode (parameter input).
all
Menu items 9 – 24
Steps 9 – 24 contain special settings.
all
After setting up step 1 to 7 the standard programming is completed. The device automatically
returns to the usual displaying mode by confirming the ‘Exit’ step. The display shows the present
tank content. Mount the device’s cover after completing the initial setup!
Programming examples
Example 1 Cellar welded heating oil tank for 6000 L of heating oil, linear steel tank.
Interior height 165 cm, (current level: 125 cm) level probe 0 - 200 mbar
Device RELAY: Relay 1 has to operate when liquid level is at 500 liters (8%):
Menu item
1. Measuring probe
2. Liquid
3. Tank shape
4. Tank volume
5. Tank height
5b. Filling limit
6. View
7. Relay 1
Relay 2
8. Exit [Enter]
Input
200 mbar
Heating oil
Linear
6000 Liters
165.0 cm
95%=157cm
Fillspace + cm Level (displayed in line 2)
Active => On = 8% ; Off = 10%
Deactive
Displaying mode => ... 4550 L ... 76 %
Example 2 Buried tank, cylindric horizontal, for 100600 liter of diesel oil,
Interior height 2.88 m, (current level 54 cm), level probe 0 - 250 mbar
Device DATA GSM with SIM card:
Menu item
1. Measuring probe
2. Liquid
3. Tank shape
4. Tank volume
5. Tank height
6. View
7. Relay
8. ( Exit )
. . .
15. Modem
. . .
19. Exit [Enter]
Input
250 mbar
Diesel oil
Cyl. horizontal > 50 000 L
100600 L (exact value of bearing chart)
288.0 cm (exact value of bearing chart)
Fillspace + Percent (displayed in line 2)
Deactive
Jump to the next step by pressing [+]
...
PIN: xxxx - Enter the PIN code of the SIM-card.
...
Displaying mode => ... 12 800 L ... 13 %