Instructions
P. 6
Setup and Operation
Version 04-2017
Input function:
Menu main item
Description
For which
device
4. Tank volume
Enter the tank volume by [+] [-]. ( 100% value)
Preadjustment is 0 L . The value must be entered.
In case of tanks > 1.000.000 units see menu item 12 too.
Attention:
If a bearing chart is available, please utilize total value.
For a buried tank of ~100 m
3
it may be e.g. 100600 liters.
all
5. Tank height
5b. Filling limit
Enter the interior height of the tank in cm: e.g. 249.0 cm
Attention: If a bearing chart is available it is recommended
to take the max. value pair out of the chart.
E.g. in case of a 100 m
3
buried tank (subgrounded)
the exact value could be 288.6 cm.
Enter the filling limit of the tank:
Oil tanks mostly have a filling limiter which defines the
filling stop point. The default value is 95%.
If for example a large water tank can be filled to its
upper rim then enter 99%.
e.g. Filling limit: 95%=190cm Change value by + / -
all
6. View
The upper display line shows the tank name and inventory
in Liters (depending on selection in menu item 12).
Select the displaying in display line 2:
View details: a) Fillspace+Percent
b) Fillspace+Level (cm)
c) Percent+Level (% + cm)
For oil tanks a) or b) is recommended to show the
fillable free space up to the limiter.
- collective - Displaying tanks without shifting over.
Liters of tank 1 to tank n will be
displayed together, see page 2.
- single/detailed - All connected tanks are shown in
detail by shifting over one by one.
L + % (+ temperature) are displayed.
- total sum Σ: Y/N Displays whole inventory of all tanks
beside the single tanks details, see p.2
All
Only for
QUATTRO
QUATTRO GSM
NET
QUATTRO NET
7. Relay
or Exit
Switching function of relay 1: Inactive / Active / On / Off
- Inactive Effect: The relay does not operate depending
on the contents. No relay state is
displayed or comes with the messages.
- Active Effect: The relay operates depending on the
contents level.
- On Makes the relay operate ( fix ON, closed ).
- Off Makes the relay release ( fix OFF ).
Example: Switching point setup for ’Active’ (with hysteresis):
On 10% - Enter relay‘s operating point by + / -
Off 15% - Enter relay’s releasing point by + / -
RELAY
DATA GSM
NET
On +35°C - Enter relay’s operating point by + / -
Off +45°C - Enter relay’s releasing point by + / -
The relay is without switching function if both values are set
to 0% and the temperature switching points are set to 0°C.
RELAY
DATA GSM
NET