Instructions

P. 4
Setup and Operation
Version 04-2017
Setup / Programming
To enter the setup menu press the [Enter] pushbutton.
The setup menu consists of the basic menu items 1 to 7.
The specific menu items 9 to 24 contain extra adjustments.
The device types QUATTRO, QUATTRO NET and QUATTRO GSM are compatible to link and
display more than one measuring probe. In this case the number of the tanks is requested before
the menu is entered.
Press [Enter] one time and then select the number of the tank by pressing [ + ] / [ - ].
The following parameter adjustments refer to that tank number.
Press [ + ] to navigate to a particular menu item. Enter the parameterization of a particular menu
item by pressing [Enter] and confirm the selected value.
Input function:
Menu main item
Description
For which
device
Preselection of tank
number i
For more than one linked tank / measuring probe:
select ‘Tank number 1’ ... up to ‘Tank number 4’.
QUATTRO GSM
QUATTRO NET
QUATTRO
0. Exit
Entering the programming mode. Use [+] to go further.
Also leaving the programming. Leave with [OK].
all
1. Measure probe
Setup range of the level probe:
Range: Max.height of oil tank Water column
100 mbar 1,25 m 1,00 m
150 mbar 1,85 m 1,50 m
200 mbar 2,50 m 2,00 m
250 mbar 3,00 m 2,50 m
400 mbar 4,90 m 4,00 m
500 mbar 6,00 m 5,00 m
1000 mbar 12,0 m 10,0 m
2000 mbar 20,0 m
5000 mbar 50,0 m
Or ‘Set mbar’, for specific measuring range of the probe.
‘By calibration’ is displayed when ‘Trim height’ has been exe-
cuted in menu item 10. (Probe range is not relevant then.)
( all )
Select the
pressure
range of
the measure
probe.
Do not enter
the liquid
level here.
2. Liquid
Selection of measuring liquid (specific weight of the liquid):
Heating oil, water, diesel oil , bio diesel oil, AdBlue, motor oil,
RME/FAME, rapeseed oil, palm oil*, gasoline*, ...
Or enter the ‘Density value’ in xxx kg / m
3
. Use [+] [-].
If the density value of the liquid is unknown calibrate the
device via menu item ‘10.Trim height’
‘By calibration’ is displayed when ‘Trim height’ has been
executed in menu item 10. In that case the parameter
‘Liquid’ (resp. density) is not relevant.
all
* = with special
type of probe