Instructions
Version 04-2017
Setup and Operation
P. 11
Additional
input functions:
Description
For which
device
18. Language
Language :
. . .
‘German’ / ‘English’ / ‘French‘ / ‘ESC’,
use + / - / Enter
all
all
Names :
. . .
Name and characters are overwriteable.
Characters changeable by + / - / Enter
- Tank 1: abcabc
- Tank n: xyzxyz
- Alarm name: Alarm A
19. Exit
Press [Enter] for returning to the displaying mode.
all
20. LCD display
By factory setup the contrast of the LCD display is a
hexadecimal value of e.g. 24 . Contrast: xx
all
21. Device info
Shows
Software version : V6.00 (+) ( e.g. )
Serial no. : Tank i: SN=1234 ( i = tank no.)
Offset + Gain : X0=2980 B=1268 ( for tank i )
all
22. Test current
Testing function for the current mA signal of the
measuring probe: e.g. ADC = 28A1 = 4.01 mA
In case of unplunged measuring probe the value should be
close to 4 mA. Tolerance range is 3.7 ... 4.3 mA.
If out of tolerance range, see menu item 9.Offset probe.
all
23.Test relay
Testing function for relay switching:
Relay 1 = Off / On + / - / Enter
Same for Relay 2 at device type RELAY. + / - / Enter
RELAY
DATA GSM
NET
24. Reset
Resetting of the device software:
- ESC : Leaves this sub-menu without execution.
- Restart : New initialization of the device software
but parameter setup is left unchanged.
- Factory setting: Complete resetting and clearing of all
parameters back to the original state of delivery.
all
25. Configuration
Internal controlling parameters. Sensitive! Don’t change them.
Exit with ’Cfg:0’ [Enter]
all
26. Exit
Return to displaying mode…
all