Instructions

P. 10
Setup and Operation
Version 04-2017
15. Network
or
15. Modem
NET, QUATTRO NET : - DHCP . . .
Sub-menu for network parameter setup
like IP addresses, message destination
and communication test.
Please coordinate these settings
with your network admin.
See additional documentation
’network device connection’.
DATA, QUATTRO GSM: - Send SMS . . .
A test SMS will be sent to the mobile
number set by #T command.
See additional documentation
‘Messages, Commands a. Parameters’.
- PIN . . . .
Shows the PIN No. of the SIM card.
PIN = 0000 deactivates the internal
GSM modem completely.
Only for
NET
QUATTRO-NET
Only for
DATA GSM
QUATTRO GSM
16. Sort tanks
/ Clear tank
‘ESC’ / ‘Tank n’ Deletion of a registered tank:
If the QUATTRO-xxx device detects a
measure probe signal at the next input
then this tank becomes registered at
the next tank number (tank n).
Here you may re-sort or delete the registered tank numbers.
Only for
QUATTRO
QUATTRO GSM
QUATTRO NET
17. Input/Output
Alarm-In :
. . .
Choose the function of the alarm contact input:
- Deactive Defines the alarm input to
not operating.
- Opening If input contact opens for > 2 min.
then the alert will be triggered.
- Closing If input contact closes for > 2 min.
then the alert will be triggered.
DATA GSM
NET
QUATTRO
DATA GSM
QUATTRO GSM
NET
QUATTRO NET
Data-Out :
. . .
Defines the data output at the adaptor slot.
Choices are:
- Output of single tank data T1 / T2 / T3 / T4
=> Applicable for analogue adaptor.
- Output of all tanks T1 T4
=> Data of all tanks sequentially go
to the output,
- e.g. via the ‘serial output adaptor’
to PC-LINK or to H-Protocol-Box
- or for the MBus Adaptor.