6/ 6HFXULW\ 6\VWHP ,QVWDOODWLRQ DQG 6HWXS *XLGH ARMED 1 OFF 2 AWAY READY 4 MAX 5 TEST 6 BYPASS 7INSTANT 8 CODE 9 CHIME * 0 # READY 3 STAY ARMED 1 OFF 2 AWAY 3 STAY READY 4 MAX 5 TEST 6 BYPASS 7INSTANT 8 CODE 9 CHIME * N7526–8V1 3/00 READY 0 #
. ii
RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations for Smoke and Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
Table of Contents Table of Contents List of Figures .....................................................................................................................................................vii Conventions Used In This Manual ............................................................................................................... viii SECTION 1 Introduction .................................................................................................................................
Table of Contents SECTION 8 4285 & 4286 VIP Module ............................................................................................................8–1 About the 4285 & 4286 VIP Module ...............................................................................................................8–1 Installing the Phone Module...........................................................................................................................8–1 Programming the 4285/4286 VIP Module ..........
Table of Contents SECTION 18 Zone Lists ..................................................................................................................................18–1 About Zone List Menu Mode .........................................................................................................................18–1 Zone List Displays .........................................................................................................................................
List of Figures Figure 1. Installing the Cabinet Lock.................................................................................................................2–1 Figure 2. Mounting the PC Board.......................................................................................................................2–2 Figure 3. Mounting the PC Board and RF Receiver Together in the Cabinet .................................................2–3 Figure 4. Telephone Line Connections ..........................
Conventions Used In This Manual Before you begin using this manual, it is important that you understand the meaning of the following symbols: UL A UL note includes specific information that must be followed if you are installing this system for a UL Listed application. A checked note includes information you should be aware of before continuing with the installation, and which, if not observed, could result in operational difficulties.
S E C T I O N 1 Introduction • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ General Description ♦ Features • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • General Description The SL150 is a security system control that supports up to 38 zones, including eight basic hardwired zones (1 through 8) and a maximum of 30 expansion zones.
SL150 Installation and Setup Guide Security Codes • One Installer code for entire system (user 1) • One Master code for entire system (user 2) • 12 Secondary User codes (users 3–14) • One Babysitter code (user 15). • One Duress Code (user 16). Baby-sitter Code: A special code that can only be used to disarm the system if that particular code (or the installer code) was used to arm it. Generally assigned to a babysitter or cleaner.
Section 1 - Introduction Optional Phone Module • Supports the Ademco 4285/4286 VIP Module (refer to Section 8 for further information). • Provides access to the system via on-premises or off-premises phones for arming, disarming, etc., plus control of relay outputs and Powerline Carrier devices. Paging Feature If programmed, the paging feature allows certain system conditions to be reported to two pagers, if desired. Up to 16 digits may be programmed to be sent as a userdetermined message to each pager.
SL150 Installation and Setup Guide Dynamic Signaling Feature This control features Dynamic Signaling Delay and Dynamic Signaling Priority message reporting when Long Range Radio is used. This feature, which is programmed in data fields ✱54 and ✱55, is designed to reduce the number of redundant reports sent to the central station. Field ✱29, OUTPUT TO LONG RANGE RADIO, must be enabled for this feature to function.
S E C T I O N 2 Installing the Control • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Mounting the Cabinet ♦ Standard Phone Line Connections ♦ Installing the Lock ♦ Wiring the AC Transformer ♦ Mounting the Control's Circuit Board Alone in ♦ Installing the Backup Battery the Cabinet ♦ Earth Ground Connections ♦ Mounting the Control and RF Receiver Circuit Boards Together • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
SL150 Installation and Setup Guide Before installing the cabinet's contents, remove the metal cabinet knockouts required for wiring entry. Do not attempt to remove the knockouts after the circuit board has been installed. Mounting the Control's Circuit Board Alone in the Cabinet To mount the circuit board alone in the cabinet, follow these steps: 1. Hang two short natural-colored mounting clips (provided) on the raised cabinet tabs (see Detail B in Figure 2). 2.
Section 2 - Installing the Control 5. Swing the base of the board into the mounting clips and secure it to the cabinet with the accompanying screws (see Detail B). 6. Insert the top of the control's board into the slot in the clips and position two long (red) clips at the lower edge of the board (see Detail C). 7. Swing this board into place and secure it with two additional screws. 8.
SL150 Installation and Setup Guide Standard Phone Line Connections The wiring connections shown here are not applicable if the4285/4286 VIP Module is used. Refer to Section 8: 4285/4286 VIP Module for information regarding phone line connections, which are different than those shown here. Incoming phone line and handset wiring is connected to the main terminal block (via an RJ31X jack) as follows and shown in Figure 4: Term. 21: Term. 22: Term. 23: Term.
Section 2 - Installing the Control Wiring the AC Transformer 1321 Transformer Wire the 1321 Transformer to terminals 1 and 2 on the control board. See wiring table below to determine wire gauge. Use caution when wiring the transformer to the control panel to guard against blowing the fuse inside the transformer (the fuse is nonreplaceable).
SL150 Installation and Setup Guide Installing the Backup Battery If necessary, refer to Section 12: Final Power-Up for information regarding battery size to use. Do not attach the connector cable to the battery terminals until you are instructed to do so later in the manual. Install the backup battery as follows: 1. Place the 12-volt backup battery in the control cabinet. 2. Attach red and black wires on the battery connector cable as follows: a.
S E C T I O N 3 Installing Remote Keypads • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Keypads That May Be Used ♦ Supplementary Power for Additional Keypads ♦ Wiring to the Keypads ♦ Preliminary Checkout Procedure ♦ Mounting the Keypads • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Keypads That May Be Used Up to 8 keypads may be used in the system, independent of auxiliary p
SL150 Installation and Setup Guide The length of all wire runs must not exceed 1500 feet (457m) when unshielded quad conductor cable is used (750 feet if shielded cable is used). This restriction is due to the capacitive effect on the data lines when quad cable is used. 2. Run field wiring from the control to the keypads (using standard 4-conductor twisted wire cable of the wire gauge determined in step 1). 3. Connect remote keypads to terminals 4, 5, 6, and 7 on the control board, as shown in Figure 6.
Section 3 – Installing Remote Keypads Make connections directly to the screw terminals as shown in Figure 7. Make no connection to the keypad blue wire (if present). Be sure to connect the negative (–) terminal on the Power Supply unit to terminal 4 (AUX – ) on the control. SUPPLEMENTARY POWER SUPPLY CONTROL TERMINAL STRIP – AUX. AUX. DATA DATA – + IN OUT 7 TO KEYPAD YEL WIRE 6 TO KEYPAD GRN WIRE IMPORTANT: MAKE THESE CONNECTIONS DIRECTLY TO SCREW TERMINALS AS SHOWN.
SL150 Installation and Setup Guide 3–4
S E C T I O N 4 Basic Hardwired Zones 1–8 • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Installing the Hardwired Zones ♦ Programming Hardwired Zones ♦ Keyswitch Installation ♦ Checkout Procedure for Hardwired Zones • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Installing the Hardwired Zones Common Characteristics of Zones 1–8 • EOLR-supervised zones support both open-circuit
SL150 Installation and Setup Guide 2. If an EOL resistor is presently connected across zone 1 terminals, remove it. The EOL resistor must be connected across the loop wires at the last detector UL In UL installations, only zone 1 may be used as a fire zone. In addition, an Ademco Model 610–7 must be used as the end-of-line resistor at the last detector. The alarm current provided by zone 1 will support only one smoke detector in the alarmed state.
Section 4 – Basic Hardwired Zones Remove 2000 ohm EOL resistor if connected across the selected zone terminals. You must connect the EOL resistor across the loop wires at the last detector. To supervise power, we recommend the use of a System Sensor No. A77-716B Supervisory Module.
SL150 Installation and Setup Guide Wiring 2-Wire Latching Glass Break Detectors On Zone 8 Use zone 8 for connection of compatible 2-wire latching-type glass break detectors. After an alarm, the first code + OFF turns off the siren and disarms the system; the second code + OFF clears the memory of alarm and resets the glassbreak detector. 1. Connect all detectors in parallel across zone 8 (terminals 19 and 20). Remove 2000 ohm EOL resistor if connected across the selected zone terminals.
Section 4 – Basic Hardwired Zones Remote Keyswitch (Zone 7) An optional remote 4146 keyswitch for remote arming and disarming of the system can be installed in this system. Included here are instructions for connecting the keyswitch, the necessary programming required, plus a description of how the keyswitch operates in the system. The remote 4146 keyswitch (with red and green LEDs to indicate status) is connected to zone 7. Remote Keyswitch Connections 1.
SL150 Installation and Setup Guide 9-PIN CONNECTOR ON CONTROL PANEL 9 BLUE BLACK 7 8 BROWN RED GREEN WHITE 3 4 5 6 YELLOW VIOLET GRAY 1 2 4146 KEYSWITCH 4142TR CABLE (ARMED) RED YELLOW THESE WIRES NOT CONNECTED IF 4300 INTERFACE TRANSFORMER IS NOT BEING USED (READY) GREEN WHITE 820 ohms = WIRE NUT 820 ohms TAMPER SWITCH (N. C.) BROWN 18 BROWN ZONE 7 ON CONTROL BOARD LOCK SWITCH (N. O.) BLUE 19 BLUE EOLR 2000 ohms Figure 11.
Section 4 – Basic Hardwired Zones Programming For The Remote Keyswitch 1. Using a 2-line Alpha keypad, enter the programming mode by entering: Installer code + 8 + 0 + 0 keys. If RF zones, wired expansion, or a keyswitch will be used, data fields ✱22 RF SYSTEM, ✱25 WIRED ZONE EXPANSION and ✱30 KEYSWITCH ENABLE must be programmed as required prior to continuing. Note: If keyswitch is enabled, in menu mode ✱56 the Zone Type (ZT) for zone 7 will show “77”, and will not be accessible for programming. 2.
SL150 Installation and Setup Guide Typical summary display Zn ZT RC In 07 77 3C HW: 1 A summary display will appear, showing the data for zone 07 that was just programmed. If it is programmed satisfactorily, press [✱] to continue. RT The next request is to enter an Alpha descriptor for zone 7. Since this is a keyswitch zone, no descriptor is required. Enter “0”.
Section 4 – Basic Hardwired Zones 3. Fault and then restore every contact or sensor on each zone individually to ensure that it is being monitored by the system. Each time a zone is faulted, the keypad should display the number of the faulted zone. When each zone is restored, the SYSTEM READY message should appear again. You will need to observe the keypad as each zone is faulted and restored. When you get the proper displays on the keypad(s), the hardwired zones in the system are functioning properly.
SL150 Installation and Setup Guide 4–10
S E C T I O N 5 Wired Zone Expansion • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Installing Zone Expansion Units ♦ Programming Wired Expansion Zones ♦ Connections and Setup ♦ Checkout Procedure for Wired Expansion Zones • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Installing Zone Expansion Units You can add 8 wired EOLR zones to the basic control's 8 zones, for a total of
SL150 Installation and Setup Guide DIP SWITCH FOR SETTING ADDRESS AND ZONE A RESPONSE TIME 4-PIN CONSOLE PLUG (CONNECTIONS SAME AS TB2) 4219 TB2 GRN DATA OUT TO CONTROL BLK (–) GROUND 4 REED (TAMPER) SWITCH 4 3 2 TB1 2 1 4 3 6 5 8 7 9 1 12 11 10 TAMPER JUMPER POSITION 229 IN CABINET (NOT TAMPERED) C B A 4229 REMOTE (TAMPERED PROTECTED) E D G F 3 RED 2 (+) 12VDC YEL DATA IN FROM CONTROL 1 TERMINATE EACH PROGRAMMED ZONE WITH 1000 OHM (1K) END-OF-LINE RESISTOR (EACH ZONE'S LO
Section 5 –Wired Zone Expansion Programming Wired Expansion Zones Each zone must be programmed into the system using either the ✱56 Zone Programming mode or the ✱58 Expert Programming mode, either of which assigns characteristics that define the way the system responds to faults on that zone. Refer to Section 14: Zone Response Type Definitions and Section 16: Zone Programming for specific instructions on programming wired expansion zones.
SL150 Installation and Setup Guide 5–4
S E C T I O N 6 Wireless Expansion (5800 System) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ About Wireless Expansion ♦ About Jam Detection and Reporting ♦ Installing the 5881/5882 Receiver ♦ 5800 Series Transmitters ♦ Installing the 5800TM Module ♦ Installing 5800 Series Transmitters • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Wireless Expansion In addition to it
SL150 Installation and Setup Guide Installing the 5881/5882 Receiver RF System Installation Advisories Follow the guidelines below when installing the RF receiver. (Disregard if the receiver is mounted in the control cabinet • Place the RF receiver in a high, centrally located area for best reception. • Do not locate the receiver or transmitters on or near metal objects. This will decrease range and/or block transmissions.
Section 6 - Wireless Expansion Installing the 5800TM Module Installation of this module is necessary only if you are using one or more 5827BD wireless bidirectional keypads, 5804 or 5804BD transmitters (wireless keys). Mounting the 5800TM Module The 5800TM must be located next to the RF receiver (between one and two feet from the receiver’s antennas). The 5800TM must not be installed within the control cabinet. Mount the unit using its accompanying mounting bracket.
SL150 Installation and Setup Guide For button transmitters (RF “keys”), such as the 5801, 5804, and 5804BD, you must assign a unique zone number to each individual button used on the transmitter. Each button on the transmitter also has a pre-designated loop or input number, which is automatically displayed on the keypad. Programming an RF House ID Programming an RF House ID (01–31) in field ✱24 is necessary only if you are using 5827, or 5804BD.
Section 6 - Wireless Expansion Some transmitters (e.g., 5802, 5802CP) contain long-life but non-replaceable batteries, and no battery installation is required. At the end of their life, the complete unit must be replaced (and a new serial number enrolled by the control). Button-type transmitters (such as 5801, 5802, 5802CP) should be periodically tested for battery life. The 5802MN and 5804 Button Transmitters have replaceable batteries.
SL150 Installation and Setup Guide 5800 Series Transmitters Table Also refer to Appendix A for transmitter input loops/button locations. Model Description Input Type and Special Notes 5801 Wireless Panic Transmitter 5802 5802CP Pendant Belt Clip (Personal Emergency) Transmitters Miniature Personal Emergency Trans. Wireless Key Transmitter Enroll as “3” for RF (supervised), or “4” for UR (unsupervised). Unit has 4 pushbuttons, each with a unique input (loop) code.
Section 6 - Wireless Expansion Installing 5800 Series Transmitters The following should be performed after the transmitters have been enrolled into the system. To be sure reception of the transmitter's signal at the proposed mounting location is adequate, perform a Go/No Go Test. Go/No Go Test Mode The Go/No Go Tests will verify adequate RF signal strength from the proposed transmitter location. They allow you to reorient or relocate transmitters, if necessary, before mounting the transmitters permanently.
SL150 Installation and Setup Guide 6–8
S E C T I O N 7 Relay Outputs & Powerline Carrier Devices • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ About Relays and Powerline Carrier Devices ♦ Powerline Carrier Devices ♦ 4204 and 4229 Relay Modules ♦ Programming Relay Outputs • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Relays and Powerline Carrier Devices Relays and Powerline Carrier devices (such as X10 brand
SL150 Installation and Setup Guide 3. Connect the desired field wiring to the unit's relay contact terminals. Supervision 4204 and 4229 modules are supervised against removal. CHECK and ZONE 09 will be displayed if a module is disconnected from the control’s terminals (4, 5, 6, and 7). CHECK and ZONE 09 will also be displayed if the module cover is removed and the tamper jumper is installed.
Section 7 - Relay Outputs & Powerline Carrier Devices SWITCH NUMBER ON ➞ ➞ ➞ ➞ ➞ 1 2 3 ➞ OFF 4204 ADDRESS SETTINGS ("—" means "OFF") 0 1 ON 2 3 4 5 1 2 3 4 ON — ON — ON ON — — 4 ON ON ON 5 ON ON ON SWITCH SHOWN FOR ADDRESS "0" 5 6 7 8 9 10 11 12 ON — ON — ON ON — — ON — — — ON ON ON ON 13 14 15 ON — ON — ON ON — — ON — ON — ON ON — — ON ON ON — ON — — — ON — — — — — — — — — EITHER OR BOTH CAN BE USED TB2 4204 DIP S
SL150 Installation and Setup Guide Wiring Connections To wire the Powerline Carrier Device to the control panel, perform the following steps: 1. Splice one end of a 3-conductor cable to the wire ends of the 4142TR Cable supplied with the 4300 Transformer. 2. Connect the 4142TR Cable Plug to the 9-pin connector on the control (see Figure 24. Summary of Connections diagram for location of the 9-pin connector). 3.
S E C T I O N 8 4285 & 4286 VIP Module • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ About the 4285 & 4286 VIP Module ♦ Programming the 4285/4286 VIP Module ♦ Installing the Phone Module ♦ Checking 4285/4286 VIP Module Operation • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About the 4285 & 4286 VIP Module The 4285 or 4286 VIP Module is an add-on accessory for the SL150 that
SL150 Installation and Setup Guide If you are also using an Audio Alarm Verification (AAV) unit, refer to Section 11: Audio Alarm Verification (AAV) Unit for the wiring connections required when you are using both a phone module and an AAV unit. If you are not using an AAV unit, follow the wiring connections instructions in this section for the phone module. Wiring the Voice Interactive Phone (VIP) Module The 4285 or 4286 VIP Module is wired between the control panel and the premises handset(s).
Section 8 - 4285/4286 VIP Phone Module 4285/4286 VIP MODULE WIRING NOTES: • Wire the phone module exactly as shown, using a direct-connect cord and RJ31X jack. • If touch-tones are not heard when pressing keys following phone access to the security system via an on-premises phone, try reversing the pair of wires connected to terminals 3 and 4 on either phone module and the pair of wires connected to terminals 21 and 22 on the control.
SL150 Installation and Setup Guide Programming the 4285/4286 VIP Module You must program the system for use with the 4285 or 4286 VIP Module. This includes assigning a phone code and selecting words from the alpha vocabulary. Refer to the programming sections for specific programming details. Checking 4285/4286 VIP Module Operation To Check Operation From an On-Premises Phone: 1. Pick up the phone and enter the programmed 2-digit phone code.
S E C T I O N 9 External Sounders • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Compatible Sounders ♦ Sounder Supervision ♦ NFPA Requirements ♦ Testing the Sounder ♦ Sounder Connections and Power • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Compatible Sounders The following table lists external sounders that are compatible with the SL150: • Model Description Ademco AB-12
SL150 Installation and Setup Guide Sounder Connections and Power The SL150 provides a 12VDC output, which can power external alarm sounders (bells or sirens; see table of compatible sounders on previous page). This output will activate a sounder when an alarm occurs. Make connections to alarm output terminals 3 (+) and 4 (–). See “Wiring without Bell Supervision” in Figure 20 below. The total current drawn from the alarm output and the auxiliary power output, combined, cannot exceed 600mA.
S E C T I O N 1 0 Long Range Radio • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ About Long Range Radio ♦ Dynamic Signaling Feature ♦ Wiring Connections • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Long Range Radio Check availability of Models 7720PLUS or 7820 Long Range Radios.
SL150 Installation and Setup Guide Dynamic Signaling Feature This control panel features Dynamic Signaling Delay and Dynamic Signaling Priority message reporting when Long Range Radio is used. This feature, which is programmed in data fields ✱54 and ✱55, is designed to reduce the number of redundant reports sent to the central station.
S E C T I O N 1 1 Audio Alarm Verification (AAV) Unit • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ About Audio Alarm Verification ♦ Wiring Connections • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Audio Alarm Verification An Audio Alarm Verification (AAV) module, such as the Eagle 1250, is an add-on accessory that permits voice dialog between an operator at a central stati
SL150 Installation and Setup Guide CONTROL EAGLE SUPPLIED CABLE 5 21 22 23 24 25 4 EARTH GROUND RJ31X ➤ ➤ RED (R) GREEN (T) GREY (R) BROWN (T) CONTROL/ DIALER HEADER RED ON 123456 13 V+ 14 15 GND 16 BROWN 4204 RELAY 1 SHOWN OFF TO PREMISES HANDSET INCOMING PHONE LINE YELLOW DIP Switch NO NC C •• •• • NOTE: REFER TO AAV MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO SPEAKERS AND MICROPHONE. EAGLE 1250 TIP RING Figure 22.
S E C T I O N 1 2 Final Power-Up • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Earth Ground Connections ♦ Connecting the Backup Battery ♦ AC Power-Up ♦ Battery Tests • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Earth Ground Connections The designated earth ground terminal (25) must be terminated in a good earth ground for the lightning transient protective devices in this pr
SL150 Installation and Setup Guide Example: If total auxiliary device current drain is 450mA, add 100mA for the control panel, for a total of 550mA (0.55 amps); if 24-hour standby is wanted, the calculation will be: 0.55A x 24 hours = 13.2 Ampere/Hour battery needed. In this example, two 7 Amp/Hr batteries (connected in parallel) must be used. Table 1.
S E C T I O N 1 3 Mechanics of Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ About Programming ♦ Interactive Mode Programming ♦ Entering Program Mode ♦ Loading Factory Defaults ♦ Programming a Data Field ♦ Programming System Setup Fields ♦ Reviewing a Data Field/Erasing an Entry ♦ Exiting the Programming Mode • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About
SL150 Installation and Setup Guide Entering Program Mode You may use one of the following methods: a) Press [✱] and [#] keys at the same time within 50 seconds after power is applied to the control; or b) After power-up, enter 4 1 1 2 (Installer code) + 8 0 0. This method is disabled if you exit the Program mode using ✱98 instead of ✱99. See the paragraph titled, Exiting the Program Mode, later in this section.
Section 13 - Mechanics Of Programming Loading Factory Defaults The control panel is shipped from the factory loaded with its factory defaults. To reload the factory defaults at any time, enter the Programming mode, press ✱97, then exit the Programming mode.
SL150 Installation and Setup Guide 13–4
S E C T I O N 1 4 Zone Response Type Definitions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Zone Type Definitions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Zone Type Definitions You must assign to each zone, a zone type, which defines the way in which the system responds to faults in that zone. Zone types are defined below.
SL150 Installation and Setup Guide Type 04 Interior Follower This zone type gives a delayed alarm (using the programmed entry/exit time) if the entry/exit zone is faulted first. Otherwise this zone type gives an instant alarm. This zone type is active when the panel is armed in the AWAY and MAXIMUM modes. This zone type is bypassed automatically when the panel is armed in the STAY or INSTANT mode.
Section 14 - Zone Response Type Definitions Type 10 Interior w/Delay This zone type gives Entry Delay (using the programmed entry time), if tripped when the panel is armed in the AWAY mode. Entry Delay begins whenever sensors in this zone are violated, regardless of whether or not an Entry/exit Delay zone was tripped first. No Entry Delay is provided if tripped when the panel is armed in the MAXIMUM mode. Exit Delay is present for any arming mode.
SL150 Installation and Setup Guide 14–4
S E C T I O N 1 5 Data Field Descriptions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Descriptions of System Data Fields • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Descriptions of System Data Fields The blank programming form (in the Programming Guide) should be used to record the data for this installation. Defaults (where applicable) are indicated in the programming form.
SL150 Installation and Setup Guide ✱25 WIRED ZONE EXPANSION 0 0 = no expander module connected 1 = 4219 connected 2 = 4229 connected 3 = 4204 connected ✱26 CHIME BY ZONE 0 0 = no (chimes on fault of any entry/exit or perimeter zone when chime mode activated) 1 = yes (chimes on fault of specific zones programmed in relay zone list 3 when chime mode activated) This option allows the installer to define the specific zones intended to chime when faulted while the system is in chime mode.
Section 15 -Data Field Descriptions ✱30 0 KEYSWITCH ENABLE (ZONE 7) 0 = disable; 1 = enable A keyswitch can only be used on zone 7. See Section 4–Basic Hardwired Zones for installation details.
SL150 Installation and Setup Guide ✱38 0 CONFIRMATION OF ARMING DING 0 = no ding 1 = confirmation ding after arming system 2 = confirmation ding after arming from RF button type units or RF keypad only (ding occurs when the system receives the RF transmission) Confirmation of arming is ½-second external sounder “ding” when closing report is sent, or at the end of Exit Delay.
Section 15 -Data Field Descriptions ✱47 3 PHONE SYSTEM SELECT If Central Station is NOT on a WATS line: 0 = Pulse dial, 1 = Tone dial If Central Station IS on a WATS line: 2 = Pulse dial, 3 = Tone dial ✱48 REPORT FORMAT 7 | 7 0 = 3+1, 4+1 Ademco LOW SPEED STANDARD 1 = 3+1, 4+1 RADIONICS STANDARD 2 = 4+2 Ademco LOW SPEED STANDARD 3 = 4+2 RADIONICS STANDARD 6 or undefined = 4+2 Ademco EXPRESS 7 = Ademco CONTACT ID REPORTING 8 = 3+1. 4+1 Ademco LOW SPEED EXPANDED 9 = 3+1.
SL150 Installation and Setup Guide ✱53 0 SESCOA/RADIONICS SELECT 0 = Radionics (0–9, B–F reporting) 1 = SESCOA (0–9 only reporting) Select 0 for all other formats. ✱54 DYNAMIC SIGNALING DELAY (DSD) See chart below 0 This field enables you to select the time the panel should wait for acknowledgment from the first reporting destination before it attempts to send a message to the second destination. Delays can be selected from 0 to 225 seconds, in 15-second increments. This delay is per message.
Section 15 -Data Field Descriptions TO PROGRAM SYSTEM STATUS AND RESTORE REPORT CODES (✱59 –✱76, & ✱89) Report codes can be programmed using the interactive ✱56 Zone Programming Mode or ✱58 Expert Mode, or codes can be entered in data fields ✱59 - ✱ 76, ✱ 89. The following is a set of guidelines to be used for programming report codes.
SL150 Installation and Setup Guide ✱60 1 | 0 TROUBLE REPORT CODE (See box on previous page) This will be sent if a zone goes into trouble. ✱61 0 | 0 BYPASS REPORT CODE (See box on previous page) This will be sent when a zone is manually bypassed. ✱62 0 | 0 AC LOSS REPORT CODE See box on previous page. Reports with subscriber number. Timing of this report is random with up to a 4-hour delay. If AC restores before the report goes out, there is no “AC Restore” report.
Section 15 -Data Field Descriptions ✱72 BYPASS RESTORE REPORT CODE 0 | 0 See box on a previous page. This is sent when a zone that has been bypassed is unbypassed. ✱73 AC RESTORE REPORT CODE 0 | 0 This is sent when AC power has been restored after an AC power outage. See box on a previous page. Reports with subscriber number. ✱74 LOW BAT RESTORE REPORT CODE 1 | 0 This is sent when a system low-battery condition is restored to normal. See box on a previous page. Reports with subscriber number.
SL150 Installation and Setup Guide ✱84 0 PAGER REPORTS 0 0 = No reports sent Pgr 1 Pgr 2 1 = Open/close for all users 3 = Open/close for users 5-16 and wireless key zones entered in zone list 6/7* 4 = All alarms and troubles 5 = All alarms, troubles, and open/close for all users 7 = All alarms, troubles, and open/close for users 5-16, and wireless key zones entered in zone list 6/7* 12 = Alarms and troubles for zones entered in zone list 6/7* 13 = Alarms and troubles for zones listed in zone list 6/7*,
Section 15 -Data Field Descriptions ✱87 PAGER #2 PHONE NO. | | | | | | | | | | | | | | | | | | | Enter up to 20 digits. If you enter fewer than 20 digits, exit by pressing [✱] and next field number. To clear entries from this field, press ✱87✱. ✱88 PAGER #2 CHARACTERS | | | | | | | | | | | | | | | Up to 16 characters may be sent as a prefix to the 7-digit system status code sent to pager #2 (if used). Phone number in field ✱87 must have been entered.
SL150 Installation and Setup Guide ✱91 OPTION SELECTION 8 0 = not using AAV 2 = Macros (speed key) 4 = an Audio Alarm Verification (AAV) unit is connected to the system 8 = enable Exit Delay restart 12 = both AAV and Exit Delay Restart 14 = enable all UL installations: Must be 0 (AAV disabled) ✱92 PHONE LINE MONITOR ENABLE 0 0 = not used 1 = local keypad display only when phone line is faulted 2 = local keypad display plus keypad trouble sound when line is faulted; no automatic timeout.
Section 15 -Data Field Descriptions ✱95 RING DETECTION COUNT FOR DOWNLOADING 15 0–15 = number of rings before control picks up phone line Refer to the chart below and program this field accordingly. Phone Module Answering Machine Downloading Field ✱95 Yes No No Set for value other than 0 (1–14). This will enable the control panel to answer the phone call. Otherwise, it will not be possible to access the phone module.
SL150 Installation and Setup Guide 15–14
S E C T I O N 1 6 Zone Programming (✱56/✱58 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ About Zone Programming ♦ To Remove a Zone ♦ ✱56 Zone Programming Procedures ♦ To Delete a Transmitter Serial Number ♦ ✱58 Expert Programming Mode Procedures ♦ To Enter and Duplicate Wireless Keys • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Zone Programming ✱56 Zone
SL150 Installation and Setup Guide È Zone Number 10 Zone Type Perimeter 03 Zone Type Ç Zone Type (ZT): Enter the Zone Type response (or change it, if necessary). Each zone must be assigned to a zone type, which defines the way in which the system responds to faults in that zone. Enter the Zone Type code (or change it, if necessary). Zone types are listed below. Note: If 00 is entered, Delete Zone ? will be displayed.
Section 16 -Zone Programming 10 INPUT S/N: L A022-4064 1 Note: The [A] and [B] keys may be used to move the cursor to the right (A) or left (B) within the serial number field, thus allowing you to correct any entry errors that may have been made. 10 INPUT S/N A022-4064 L ? Serial number Entry and Loop Number Entry. Used only when enrolling wireless transmitters. a. Transmit two open and close (or close and open) sequences.
SL150 Installation and Setup Guide To Delete a Serial Number → To delete an existing serial number, enter 0 in the loop number field. The serial number will change to 0's. 10 INPUT S/N: A000-0000 L 0 If 0 was entered in error, simply re-enter the loop number or press [#], and the serial number will return to the display.
Section 16 -Zone Programming Zn 10 ZT RC IN: – – –: L – Enter the first digit of the zone number to be programmed. In the example at the left where zone 10 is to be programmed, the first digit 1 is entered, followed by the 2nd digit 0. The display will show dashes, as shown at left. If zone 8 was to be programmed, you would press the 0 key, then the 8 key. You must always program zones using two digits. Use the [D] key to enter wireless keys.
SL150 Installation and Setup Guide 10 XMIT TO CONFIRM PRESS ✱ TO SKIP The prompt to confirm appears. This prompt will only appear if the first prompt on page 16-4 was answered “Yes.” To confirm, activate the loop input or button that corresponds to this zone. The system checks for duplicate. If a duplicate exists, a long error beep will sound. Press [#] to back up and re-enter the serial and/or loop number.
Section 16 -Zone Programming will not be deleted if the zone is temporarily disabled by answering “No” to the previous prompt. If only the physical transmitter is to be removed or changed (that is; its serial number deleted, as when replacing a unit that has a nonremovable battery), it can be done in ✱56 Zone Programming Mode, as indicated next.
SL150 Installation and Setup Guide ENTER START ZONE 00 = QUIT 36 Example of zone ↑ suggested by the system. This indicates that zones 36, 37, 38, and 39 are available. 6. The system will search for the highest zone number available, subtract the number of consecutive zones required for the device (four zones in the case of the 5804 and 5804BD), and display the lowest zone number of the group. If you want to start at a different zone, enter the zone desired, and press [✱].
Section 16 -Zone Programming Wireless Key Predefined Default Templates GREEN/YELLOW GRE GREEN/YELLOW LED LED LOOP 3 YOU MUST PROGRAMME THIS BUTTON LOOP 4 LOOP 2 LOOP 2 BUTTON RED/YELLOW RED/YELLOW LED LED LOOP 1 B LOOP 4 BUTTON C (YOU MUST PROGRAM THIS BUTTON) LOOP A 3 BUTTON BUTTON D LOOP 1 •• • •• •• • •• • •• • • •• •• ENROLL AS "BR" ENROLL AS "BR" 5804BD FRONT VIEW 5804 Wireless Key Transmitter 5804BD 2-Way Wireless Key Transmitter UL NOTE: These transmitters are not designed for us
SL150 Installation and Setup Guide 16–10
S E C T I O N 1 7 Output Device Programming (✱80 and ✱81 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Programming Options Defined ♦ Programming Output Relays and Powerline Carrier Devices • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Programming Options Defined The following will help you understand the programming of Output Devices when using ✱80 and ✱81 modes.
SL150 Installation and Setup Guide 2. Zone List (ZL) is a group of zones to which the event applies in order to activate a particular device. Note that there are 3 output device-related zone lists that can be programmed in ✱81 Menu mode; when the selected event (alarm, fault or trouble) occurs in any zone in the selected Start zone list (1, 2, or 3), activation of the selected device will Start. Start by Zone Type or System Operation 1.
Section 17 -Output Device Programming If a relay is energized before a 4-wire smoke detector is reset, the relay will be stopped by the interruption of Aux. Power that resets the smoke detector. If this is not desired, supply power to the relay unit from another 12V power source (e.g., the same source that is powering external equipment through the relay contacts). Programming Output Relays and Powerline Carrier Devices While in Program mode, press ✱80 to enter Output Device Menu mode.
SL150 Installation and Setup Guide 02 Start: Not Used Zn Typ 00 If a zone type or system operation will be used to START the device action, enter the appropriate 2-digit code (see table that follows). If not, enter 00. Press ✱ to continue.
Section 17 -Output Device Programming arming status of the system. To program this, do the following: 1. In ✱80 Interactive mode, choose Output Device 01 and program the Action (A) to be “2” (Close and stay closed). The Event you want to start the Device action is a fault, so program 2 in (EV). To use Zone List 1 for the 3 specific zones, program 1 in (ZL), and program these 3 zones in ✱81's Zone List 1. 2. The second condition for turning on the indicator is triggering a 24-hour aux. zone (Zone Type 08).
SL150 Installation and Setup Guide 17–6
S E C T I O N 1 8 Zone Lists (✱81 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ About Zone List Menu Mode ♦ Pager 1 Reporting - Zone List 06 ♦ Zone List Displays ♦ Pager 2 Reporting - Zone List 07 • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Zone List Menu Mode Zone List Menu mode is used to program zone lists for output devices (programmed in ✱80 Menu mode)
SL150 Installation and Setup Guide Pager 1 Reporting - Zone List 06 Pager 1 reporting is an option that must be set up using zone list 06, and entering the appropriate zones that will report to Pager 1, independent of the report code enabled. The chosen zone numbers are to be entered into zone list 06 via field ✱81. If any of the zones in zone list 06 faults in the armed state, the system will send an alarm report to Pager 1.
S E C T I O N 1 9 Alpha Descriptor Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ About Alpha Descriptor Programming ♦ Programming Zone Descriptors ♦ Zone Descriptors ♦ Adding Custom Words • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Alpha Descriptor Programming This section provides instructions for programming alpha zone descriptors.
SL150 Installation and Setup Guide Program Alpha? 0=No, 1=Yes 00 2. Press ✱82. The Program Alpha? prompt will appear. Custom Words ? 0=No, 1=Yes 00 3. Press 1 (Yes). The Custom Words ? prompt will appear. 4. Press 0 (No).* The system will then automatically display the descriptor for zone 1. * The procedure for adding custom words to the built-in vocabulary is given in "Adding Custom Words" on the next page.
Section 19 - Alpha Descriptor Programming ✳ ZN 01 BACK DOOR Ç Flashing Cursor if “6” is pressed (system is ready for next word). 9. Press 6 to accept the selected word. NOTE: If these are the only words you are using for the descriptor, press 8 instead of 6 to save them in memory. 10. The two words in our example have now been entered. Note, however, that up to three words may be entered (provided the number of characters will fit on the screen). Press 8 to save all words in memory.
SL150 Installation and Setup Guide 5. Press 8 to save the custom word(s) and return to the “CUSTOM WORD ?” display. Repeat Steps 2–5 for other custom words to be entered. To change a custom word, just overwrite it. If no more are to be entered now, press 0 to return to the Descriptor entry. The custom word(s) will be automatically added to the built-in vocabulary.
Section 19 - Alpha Descriptor Programming ALPHA VOCABULARY LIST (For Entering Zone Descriptors) 000 • 001 • 002 004 005 • 006 • 007 • 009 010 • • • • • • • 012 013 014 016 017 018 019 020 • 021 • 022 023 025 • 026 028 • 029 030 031 033 034 035 036 • 037 038 • 040 • 046 047 • 048 049 • 050 051 • 052 • 053 054 055 • 057 • 059 • 060 061 • 062 (Word Space) –A – AIR ALARM ALLEY AMBUSH AREA APARTMENT ATTIC AUDIO –B– BABY BACK BAR BASEMENT BATHROOM BED BEDROOM BELL BLOWER BOILER BOTTOM BREAK BUILDING –C– CABINE
SL150 Installation and Setup Guide 19–6
S E C T I O N 2 0 Macros (SpeedKey) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • ♦ About Macros (SpeedKey) ♦ Macro Key Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Macros The “C” key on the keypads can be used to activate a series of commands, represented by strings of up to 16 keystrokes.
SL150 Installation and Setup Guide You can enter up to 16 keystrokes to program a macro. There are no wordspaces between entries – as indicated previously, each individual command is separated by a terminator (pressing the “C” key). The keypad display echoes the keys that are pressed (see example on the previous page which shows the progression of the keypad display as each entry is made). SPEED LEARN MODE Following the entry of all commands, the full display at left will appear.
S E C T I O N 2 1 Remote Programming and Control (Downloading) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ About Remote Programming ♦ Remote Programming Commands ♦ Equipment Required ♦ Remote Programming Advisory Notes ♦ Initial Download • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Remote Programming The system can be remotely programmed from an IBM-compatible person
SL150 Installation and Setup Guide – Hayes Smartmodem Optima 2400 – Hayes Optima 2400 Fax96 – Hayes Smartmodem 1200 External Modem – Hayes Smartmodem 1200B Internal Modem (Rev. 1.2 or higher) – Hayes external Optima 24 Plus FAX96 Modem – Practical Peripherals PM14400FXSA COMPASS® Downloader Software (at revision level supporting the SL150) Appropriate interconnecting cables Initial Download For initial downloading, enter [Installer code] + # + 5.
S E C T I O N 2 2 System Communication • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Report Code Formats ♦ Panel Communication with Central Station • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Panel Communication with Central Station This system accommodates several formats for reporting alarms and other system conditions to the Central Station.
SL150 Installation and Setup Guide 3+1 and 4+1 Standard Formats Comprise a 3- (or 4-) digit subscriber number and a single digit report code (e.g. Alarm, Trouble, Restore, Open, Close, etc). Comprise a 3- (or 4-) digit subscriber number, and a two-digit report code. The first digit is displayed on the first line, followed by a second line where the first digit is repeated 3 (or 4) times and followed by the second digit. This is the “expanded” digit.
Section 22 - System Communication The Ademco Contact ID reporting format comprises a 10-digit subscriber account number, 1digit event qualifier (“new” or “restore”), 3-digit event code, and 3-digit zone number, user number, or system status number, as follows: Ademco Contact ID Reporting takes the following format: CCCCCCCCCC Q EEE ZZZ where: CCCCCCCCCC = Customer ID (subscriber account number) Q = Event qualifier, where: E = new event, R = restore EEE = Event code (3 hexadecimal digits)* ZZZ = Zone/contact
SL150 Installation and Setup Guide 22–4
S E C T I O N 2 3 System Operation • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Security Codes ♦ Keypad Functions ♦ Relay/Powerline Carrier Devices ♦ 4285/4286 VIP Module ♦ Exit Error Alarm Displays ♦ Trouble Conditions • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Security Codes Installer Code The installer programs the 4-digit Installer code initially as part of the programm
SL150 Installation and Setup Guide Notes: • All Master and Secondary User codes permit access to the system for arming, disarming, etc. • The Installer code can disarm the system only if it was used to arm it. • Babysitter code is User code No. 15; it can disarm the system only if that code (or the installer code) was used to arm it. • Duress code is User code No. 16;.
Section 23 - System Operation Wired keypads contain the following dedicated quick arming keys : No security code is required to arm the system using the A, B, or C keys. However, a security code is always required to disarm the system. A = arm AWAY B = arm STAY C = arm INSTANT (if not programmed for Macros) D = When pressed, if programmed to do so, will send a special message to a pager and display “Page in progress” on the keypad for 30 seconds.
SL150 Installation and Setup Guide Exit Error Alarm Displays (if programmed) • A display of CANCELED ALARM or CA and a zone indication will appear if an exit or interior zone contained a fault during closing at the time the Exit Delay ended (e.g., exit door left open), but the system was disarmed during the Entry Delay time. The alarm sounder and keypad sound continuously, but stop when the system is disarmed. No message will be transmitted to the Central Station.
Section 23 - System Operation Telephone Line Failure A display of CHECK 94 (on fixed-word keypads) or TELCO FAULT (on alpha keypads) indicates that a monitored telephone line (if programmed in field ✱92) has been cut (or disconnected). Depending on how the system was programmed, the keypad may also produce a trouble sound, and the external sounder may be activated. Silence by entering Installer code plus OFF.
SL150 Installation and Setup Guide 23–6
S E C T I O N 2 4 Testing the System • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Test Procedure • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Test Procedure After installation is completed, the security system should be carefully tested, as follows. 1. With the system in the disarmed state, check that all zones are intact.
SL150 Installation and Setup Guide a. TRANSMITTER SNIFFER MODE Make sure the system is disarmed before trying to enter this mode. Press [Installer code] + # + 3 on the keypad. This initiates a procedure to verify that all transmitters have been properly programmed. Note: If the communicator is in the process of sending a report to the Central Station, the system will not go into the Sniffer mode. If so, wait a few minutes, and try again.
S E C T I O N 2 5 Troubleshooting Guide • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 6<67(0 ( including SYMPTOM 1. 2. 3. 4. 5. Transmitter signal not received at 5881/5882. Transmitter zone number appears during Transmitter Sniffer mode, but does not clear. LOW BATTERY message on keypad.
SL150 Installation and Setup Guide 6<67(0 6. 7. 8. Nuisance or phantom alarm. Intrusion alarm for no apparent reason. “CHECK” and zone number 2–8 are displayed. ( including Wireless - cont 'd) POSSIBLE CAUSE SYMPTOM REMEDY 5b. If no response at all from this transmitter, this physical transmitter has not been enrolled by the system. Transmitter Sniffer display is being cleared by another unit programmed for this zone. 5b.
Section 25 – Troubleshooting Guide 602.( '(7(&725 SYMPTOM 1. Detector alarms, no apparent reason. POSSIBLE CAUSE 1a. Dust, dirt in sensing chamber. 1b. Improper location. 1c. Unit malfunctioning. 2. Detector's siren sounds. 2a. Unit not receiving required power. 2b. Unit malfunctioning. REMEDY 1a. Clean unit's sensing chamber with vacuum cleaner per unit's instructions. 1b. See unit's instructions for locations to avoid. Relocate as necessary. 1c. Replace detector. 2a.
SL150 Installation and Setup Guide 25–4
S E C T I O N 2 6 Specifications & Accessories • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • In This Section ♦ Specifications ♦ Accessories • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Specifications SL150 SECURITY CONTROL 1. Physical: 12-1/2” W x 14-1/2” H x 3” D (318mm x 368mm x 76mm) 2. Electrical: VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, Ademco No.
SL150 Installation and Setup Guide SL6150 REMOTE KEYPADError! Bookmark not defined. 1. Physical: 6-1/2” W x 5-7/8” H x 1-5/16” D (150mm x 124mm x 33mm) 2. Electrical: Voltage Input: 12VDC; Current Drain: 40 mA Standby; 70mA with ARMED LED lit, LCD backlit and sounder on. 3. Interface Wiring: Keypad Connector .....DO: Keypad Connector ....... +: Keypad Connector ....... –: Keypad Connector ...... DI: To control panel's terminal strip connection points: Terminal 7: Data Output from control to keypad.
Section 26 Specifications & Accessories 4204 RELAY MODULE 1. Physical: 6-1/2” W x 4-1/4” H x 1-1/4” D (169mm x 108mm x 32mm) 2. Electrical: Voltage Input: 12VDC; Current Drain: 15mA (Relays off) 180mA (Relays on) 3. Interface Wiring: To control panel's keypad connection points 4. Four Output Relays: SPDT Contacts, Rating: 2A max at 28VDC/AC 4229 WIRED EXPANSION/RELAY MODULE 1. Physical: 6-1/2” W x 4-1/4” H x 1-1/4” D (169mm x 108mm x 32mm) 2.
SL150 Installation and Setup Guide Ademco 747 Self-contained 12-volt siren (driver built-in) for indoor wall mount. 747F available for flush mounting. Ademco 747UL Self-contained siren (driver built-in) for indoor wall mount. UL Listed. Ademco 744 Siren driver with 6 jumper-selected sound outputs. Rated at 119dB with use of an 8-ohm 30 watt speaker. Ademco 745X3 Voice siren driver with English, Spanish, and French voice messages. Separate messages for fire and burglary. Use with 8-ohm speaker.
A P P E N D I X A 5800 RF System Wireless Transmitters • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 5800 Series Transmitter Input Loop Identification All of the transmitters illustrated on the next page have one or more unique factory-assigned input (loop) ID codes. Each of the input loops requires its own programming zone (e.g., a 5804's four inputs require four programming zones).
SL150 Installation and Setup Guide A–2
A P P E N D I X B Regulatory Agency Statements • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • UL NOTICE: This is a “Grade A” residential system. FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 15 STATEMENT This equipment has been tested to FCC requirements and has been found acceptable for use.
SL150 Installation and Setup Guide Regulatory Agency Statements (Continued) FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 68 STATEMENT This equipment complies with Part 68 of the FCC rules. On the front cover of this equipment is a label that contains, among other information, the FCC registration number and ringer equivalence number (REN) for this equipment. If requested, this information must be provided to the telephone company.
A P P E N D I X C Warnings and Limitations • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • WARNING! THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example: • Intrusion detectors (e.g.
SL150 Installation and Setup Guide Limitations of This Alarm System (Continued) • Alarm warning devices such as sirens, bells or horns may not alert people or wake up sleepers if they are located on the other side of closed or partly open doors. If warning devices are located on a different level of the residence from the bedrooms, then they are less likely to waken or alert people inside the bedrooms.
Index • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • 1011BE12M........................................................ 26–3 1321.............................................................. 1–4, 2–5 1321 AC Transformer ................................... 1–2, 7–3 1321 Transformer ............................................... 12–1 1400.................................................................... 26–4 1412.........................................
Index AC Restore Report Code.................................... 15–9 AC Transformer .................................................... 2–5 Accessories ........................................................ 26–3 Addressable Keypad ............................................ 8–1 Addressable Keypads........................................... 3–1 ADEMCO 1011BE12M ......................................... 9–1 ADEMCO 702....................................................... 9–1 ADEMCO 705-820..............
Index Deleting a Serial Number ................................... 16–7 deleting the zone list........................................... 18–1 Description............................................................ 1–1 Device Address .................................................... 5–1 dI................................................................. 3–3, 12–1 Dialer Delay (Burg/Fire)...................................... 15–5 Dialer Programming............................................
Index Memory-of-Alarm.................................................. 4–3 model 112............................................................. 4–5 Model Numbers ......................................................viii Modem................................................................ 13–1 MODEM COMM ................................................. 21–2 momentary switch................................................. 4–5 Monitored Telephone Line..................................
Index Sescoa/Radionics Select.................................... 15–6 Setting Program Fields to Default Values......... 15–13 Silent Burglary .................................................... 14–3 Silent Panic......................................................... 23–3 Single Alarm Sounding ....................................... 15–3 Sirens ................................................................... 9–2 Site-Initiated Remote Programming ................... 21–1 SL6150 ........................
Index Index-6
STEADY FOR BURGLARY/PANIC, TEMPORAL PULSE SOUNDING FOR FIRE (e.g. USE ADEMCO 702 SIREN, OR 12V BELL). SEE INSTRUCTIONS. * If ordering keypads, order by Part No. as follows: SL6150: Part No. 6150PL3 SL6150RF: Part No. 6150RFPL3 SL6160: Part No.
LIMITED WARRANTY Alarm Device Manufacturing Company, a Division of Pittway Corporation, and its divisions, subsidiaries and affiliates (“Seller”), 165 Eileen Way, Syosset, New York 11791, warrants its products to be in conformance with its own plans and specifications and to be free from defects in materials and workmanship under normal use and service for 24 months from the date stamp control on the product or, for products not having an Ademco date stamp, for 12 months from date of original purchase unles