(II ) 5 KVA UPS (ONLINE) WITH BATTERY BACKUP FOR 30 MINUTES :
Application: Power supply requirement for IP CCTV, Access Control system, Boom Barriers
and Turnstiles
Technology : IGBT, On line double conversion
Input:
• Nominal AC Input Voltage: 1 Phase 230V AC + Neutral + Earth , 50 Hz
• Line low/ High transfer: + 15%
• Frequency range: +
5%
• Power factor: >0.9
Output
• Voltage: 220VAC/ 230VAC/ 240VAC
• Voltage Regulation: +
1%
• Frequency: 50 Hz+/- 0.1%
• Output waveform: Pure sinewave
• Harmonic distortion: < 2% (linear load) / 5 % nonlinear load
• Power factor: 0.7 to unity
• Crest factor: 3:1
• Inverter overload capacity: 110% 15 min./ 125% 10 min./ 150% 1 min./ > 150% 1 sec.
• Efficiency (AC – DC): 90%
• Bypass: Static bypass
Transfer time
• Line to battery mode: 0 ms
• Battery to line mode: 0 ms
• Line to bypass mode: <5ms synchronized with mains
• Bypass to line mode : <5ms synchronized with mains
Battery
• Battery type: SMF
• Communication interface
• Standard: RS 232 port for software interface
• Optional: SNMP
Display
• Standard: 2 line x 20 characters, Backlight LCD
• AC input voltage, AC input frequency, Battery voltage, AC output voltage , AC output frequency,
AcCoutput load %, Temperature
• UPS status( Mains fail, Individual phase fail, Battery low DC high, Overload with shut down time,
Output low, Output high, Over temperature, UPS bypass)
General
• Operating temperature: 0 to 45 Deg C
• Humidity: Upto 95% RH, no condensing
• Noise level: < 60 dB @ 1 meter