16.5 Using the Walk Test
The XT30/XT50 panel provides a walk test feature that allows a single technician to test all the protection
devices connected to zones on the system. Conduct the Walk Test within 30 minutes of resetting the
panel. The Walk Test automatically ends if no zones are tripped for 20 minutes. TEST IN PROGRESS
displays at all keypads. When ve minutes remain, TEST END WARNING displays. If any areas are armed
the Walk Test does not start and SYSTEM ARMED displays.
WALK TEST
Walk Test
To conduct the Walk Test, reset the control panel by momentarily placing a jumper
on J16 then wait one minute. From the keypad, enter the code 8144. The keypad
displays WALK TEST. If the system is monitored and the communication type is
DD or NET, the system sends a System Test Begin report to the central station. All
programmed zones are included in the test.
STD (Standard Walk Test) - Select STD to Walk test zones. All programmed zones are
included in the test.
WLS (Wireless Check-in Test) - Select WLS to automatically test 1100 Series wireless
transmitter communications. Includes all wireless devices except key fobs and
transmitters programmed for a supervision time of 0 (zero).
Note: For the XT30, Wireless Check-in Test operation only displays when connected
to 1100D Wireless Receiver Version 105 or higher.
Trip Counter for Walk Test (STD)
Displays the number of zone trips during the Walk Test.
Each time a selected zone trips, the keypad buzzes and the bell rings for two
seconds.
Each time a FI, FV, or SV zone trips, a Sensor Reset occurs.
END - Press the Select key directly below END to stop the Walk Test. When the Walk
Test ends or a 20 minute time-out expires, a nal Sensor Reset occurs. The System
Test End message is sent to the receiver along with Verify and Fail messages for
each zone under test. Faulted zones then display on the keypad.
Trip Counter For DMP Wireless Check-in Test (WLS)
Displays the number of wireless zones that automatically communicate a supervisory
check-in message.
The number of zones that check in. (XX in the example).
The total number of wireless zones programmed for supervision that should
check in. (ZZ in the example).
END - Select END to stop the Wireless Check-in Test. When the test ends or
a 20-minute time-out expires, normal wireless zone processing returns. If all
transmitters check-in, both numbers will match within three (3) minutes. If a
transmitter has multiple zones (1101, 1114, etc.), all zones will be included in the
counts. Failed wireless zones will then display on the keypad.
TEST END WARNING
Test End Warning
When no zones have been tripped and ve minutes remain on the 20 minute Walk
Test timer, the keypad displays TEST END WARNING and the keypad tones. If no
additional test zone trips occur, the test ends and a nal Sensor Reset automatically
occurs. The System Test End message is sent to the receiver along with Verify and
Fail messages for each zone under WALK test. Faulted zones then display on the
keypad.
SOUTH LOBBY
Failed Zones Display
ZONE: 10 -FAIL
Each zone that did not trip at least once during the Walk Test displays on the keypad
that initiated the test. Any Fire (FI) Panic (PN) or Supervisory (SV) 24-hour zone
that is faulted at the end of the Walk Test displays a trouble condition for that zone
regardless of the message programmed for the open or short condition of the zone
and a zone trouble is sent to the receiver. Press the COMMAND key to display the
next failed zone.
For the Wireless Check-in Test, failed wireless zones display only on the keypad.
Zone Verify/Fail reports are not sent to the central station receiver for the wireless
checkin test.
CHKIN: XX/ZZ END
STD WLS
TRIPS: XXX END
WALK TEST
WIRELESS TEST