Installation guide
XT30/XT50 Programming Guide Digital Monitoring Products
33
zone informaTion
A report of a swinger bypass is sent to the receiver if Bypass Reports has been
enabled. See the Bypass Reports section.
Bypassed zones are automatically reset when the area they are assigned to is
disarmed. All bypassed 24-hour zones are reset when the system is disarmed.
13.14
PREWARN: 12345
Prewarn Address
Option is only shown for an Exit zone.
At the start of the entry delay, all keypad addresses dis play ENTER CODE:-. If you
want the prewarn to sound at all ve addresses, leave the default as shown.
To delete an address, press the matching number on the keypad. To disable
prewarning at all keypads, press a top row key to clear the addresses shown. Press
the COM MAND key when the address selection is com plete.
Note: On XT30 and XT50 systems, the prewarn tone stops at the keypad when the
rst digit of a user code is entered. If, within ve seconds, a valid user code is not
entered or an invalid user code is entered, the prewarn tone begins sounding again.
Fifteen seconds must elapse before entering a digit silences the prewarn tone again.
13.15
ENTRY DELAY: 1
Entry Delay
Option is only shown for an Exit zone. Select the entry delay timer for this zone.
Entry delay timers 1 and 2 are programmed in Entry Delay in the System Options
menu.
13.16
CRS ZONE NO YES
Cross Zone
Select YES to enable cross-zoning for this zone. Cross-zoning requires this zone to
trip twice, or this zone and another cross-zoned zone to trip, within a programmed
time before an alarm report is sent to the receiver.
Note: To operate correctly, all cross-zone zones need to be programmed as the
same zone type.
When a cross-zoned zone trips, the Output action assigned to the zone activates. See
the Bell Action section. The cross-zone time specied in System Options begins to
count down. See the Cross-Zone Time section. If another cross-zoned zone in the
system faults, or if the rst zone restores and faults again before the cross-zone time
expires, the bell turns on and the panel sends an alarm report.
If no other cross-zoned zone in the system trips before the cross-zone time expires,
the panel sends only a fault report from the rst zone to the receiver.
Note: If CRS ZONE is YES, a valid CRS ZN TIME must be programmed for this feature
to be enabled.
Cross-zoning is not compatible with Fire Verify zone types: You cannot enable
cross-zoning for Fire Verify zones.
13.17
PRIORITY NO YES
Priority
Selecting YES allows you to provide additional protection for a zone by requiring it
to be in a normal condition before its assigned area can be armed. A priority zone
cannot be bypassed.
A Priority zone not in a normal condition cannot be armed. If a user attempts to
arm the area, the keypad displays the bad zone name followed by PRIORITY ZONE
and the arming is stopped.
13.18
ZONE NO: -
Zone Number
Enter the zone number you want to program next. Return to section 11.1 and
follow the descriptions of each programming prompt. If all zones are programmed,
press the ARROW key at the ZONE NO: – display to continue.