Installation guide
Digital Monitoring Products XT30/XT50 Programming Guide
20
bell oPTionS
Bell Options
9.1
BELL OPTIONS
Bell Options
This section allows you to program the panel bell output functions.
9.2
BELL CUTOFF: 5
Bell Cutoff Time
Enter the maximum time from 1 to 15 minutes the Bell Output remains on. If the
Bell Output is manually silenced or the system is disarmed, the cutoff time is reset.
Enter zero to provide continuous bell output. Default is 5.
Note: To support the Cancel/Verify operation on an All/Perimeter or Home/Sleep/
Away system, set the Bell Cutoff Time to greater than 0.
9.3
BELL TEST NO YES
Automatic Bell Test
When YES is selected, the Bell Output is turned on for two seconds when all areas
in the system are armed. The Bell Test only occurs when the areas are armed from
a keypad. Arming performed from an Arming zone or remotely from Remote Link™
does not activate the Bell Test. In addition, the Closing Wait feature is activated if
Opening/Closing Reports is YES. See OPENING/CLOSING AND USER REPORTS.
Closing Wait operation
Closing Wait provides a delay time before a monitored system arms until the panel
receives an acknowledgment of the closing report from the central station receiver.
During the delay, the keypad displays ONE MOMENT . . . Once the closing is
acknowledged, the keypad buzzes for one second and then displays the ALL SYSTEM
ON message. If the primary communication fails, but the backup communication
is successful, then the message BACKUP ALR ONLY will appear. If both primary and
backup communication fail, the message LOCAL ALARM ONLY will appear.
9.4
BELL OUTPUT: 0
Bell Output
Enter the output number when needed to follow the panel Bell terminal 5 operation
for all action and off conditions. Enter 0 (zero) to disable.
Note: When BELL ACTION below is set to T for Temporal Code 3, this Bell Output
action is pulse for wired outputs 1-4 and wireless outputs 31-34 and 41-44.
9.5
BELL ACTION . . .
Bell Action
This denes the type of Bell Action from zone alarms that will occur on the panel’s
bell terminal number 5. Trouble conditions do not activate Bell Action. There are
seven zone types you can program individually for Bell Output. To provide a steady
Bell Output, enter S. For a pulsed output, enter P. For a Temporal Code 3 output,
enter T and for no Bell Output, enter N.
9.5.1
FIRE TYPE: P
Fire
Denes Bell Action for Fire Type Zones. The default is set at P.
9.5.2
BURGLARY TYPE: S
Burglary
Denes Bell Action for Burglary Type Zones. The default is set at S.
9.5.3
SUPRVSRY TYPE: N
Supervisory
Denes Bell Action for Supervisory Type Zones. The default is set at N.
9.5.4
PANIC TYPE: N
Panic
Denes Bell Action for Panic Type Zones. The default is set at N.
9.5.5
EMERGNCY TYPE: N
Emergency
Denes Bell Action for Emergency Type Zones. The default is set at N.
9.5.6
AUXLRY 1 TYPE: N
Auxiliary 1
Denes Bell Action for Auxiliary 1 Type Zones. The default is set at N.
9.5.7
AUXLRY 2 TYPE: N
Auxiliary 2
Denes Bell Action for Auxiliary 2 Type Zones. The default is set at N.