Installation guide
XT30/XT50 Programming Guide Digital Monitoring Products
17
SySTem oPTionS
8.6
EXIT DELAY: 60
Exit Delay
Enter the Exit Delay time for all Exit type zones. When the exit delay time starts,
all activity on exit and burglary zones is ig nored until the exit delay expires. The
keypad displays the Exit Delay time countdown and annunciates the Exit Delay tone
at 8 second intervals until the last 10 seconds when annunciation is at 3 second
intervals. The exit de lay can be from 45 to 250 sec onds. Default is 60 seconds.
During Exit Delay, if an exit zone trips, then restores, and trips again, the Exit Delay
timer restarts. This restart can occur only once.
Exit Error Operation: At arming, when an entry/exit zone (EX) is faulted at the end
of the exit delay then one of two sequences occur:
For Entry Delay 1 EX type zones:
• the bell sounds for the length of time set in Bell Cutoff programming
• the Entry Delay operation starts, requiring code entry to disarm
• if not disarmed, a zone alarm and an Exit Error are sent to the receiver.
For Entry Delay 2 EX type zones:
• the zone is force armed and a zone force arm message is sent to the receiver
• an Exit Error is sent to the receiver
• the bell sounds for the length of time set in Bell Cutoff programming
8.7
CRS ZONE TM: 0
Cross Zone Time
Enter the time allowed between zone faults. When a zone programmed for cross
zoning faults, the panel begins counting down the Cross-Zone Time entered here. If
the same zone or another cross-zoned zone faults within this time, an alarm report
is sent to the receiver.
If the Cross-Zone Time expires without the second zone fault, only a zone fault
report from the rst zone is sent to the receiver. The Cross-Zone Time can be from
4 to 250 seconds in one second increments. Enter 0 (zero) to disable the Cross-Zone
Time feature. See the Appendix.
8.8
PWR FAIL HRS: 1
Power Fail Delay
This option tracks the duration of an AC power failure. The delay time can be from
1 to 9 hours. When the AC power is off for the length of the programmed delay
time, an AC power failure report is sent to the receiver. For example, if the power
failure delay is set for two hours, then the AC power failure report will be sent
between 2-3 hours. Entering a 0 (zero) sends the AC power failure report within 15
seconds.
8.9
RST SBYP NO YES
Reset Swinger Bypass
When YES is selected, an auto matically bypassed zone is reset if it remains in a
normal condition for one complete hour after being bypassed. A report of the
automatic reset is sent to the receiver if Bypass Reports has been se lected as YES.
Default is NO. See the BYPASS REPORTS section.
8.10
PHONE ACC NO YES
Telephone Access
YES allows the use of standard DTMF telephones to arm and disarm and check the
armed status of the XT30/XT50 panel. Refer to the XT30 or XT50 User’s Guide for
complete information.