Installation guide
Digital Monitoring Products XT30/XT50 Programming Guide
16
SySTem oPTionS
System Options
8.1
SYSTEM OPTIONS
System Options
This section allows you to select system wide parameters used in the operation of
the XT30/XT50 system. A description of each System Option follows:
8.2
SYSTEM: ALL/PERIM
AREA A/P H/A
System
This congures the panel as either a four Area system, an All/Perimeter system
(Perimeter/Interior), or a Home/Away system (Perimeter, Interior, and Bedrooms).
Zones must be assigned to Bedrooms for the area to be active.
When using wireless zones for an Area or All/Perimeter system, the keypad trouble
buzzer resounds every four hours when wireless zone trouble or wireless low battery
is displayed.
8.3
CLS CODE NO YES
Closing Code
When YES is selected, a code number is required for system arming. If NO is
selected, a code number is not required for system arming. Default is NO.
8.4
CLS CHK NO YES
Closing Check
Select YES to enable the panel to verify that all areas have been armed after a
schedule expires. If the Closing Check nds any areas disarmed past the scheduled
time, all keypads emit a steady beep and display CLOSING TIME!. The user must
extend the schedule or arm the system within 10 minutes or a Late to Close
message will be sent to the central station. Default is NO.
8.5
ENTRY DLY 1: 30
ENTRY DLY 2: 60
Entry Delay 1
Enter the entry delay time for all exit type zones programmed to use Entry Delay 1.
When an armed Exit type zone is faulted, the keypad prewarn tone begins sounding.
ENTER CODE:- and the name of the zone causing the Entry Delay displays on all
keypads.
When the rst digit of a code is entered, the prewarn tone stops at the keypad.
If, within ve seconds, a valid user code is not entered or an invalid user code is
entered, the prewarn tone begins sounding again. Fifteen seconds must elapse
before entering a digit silences the prewarn tone again.
The area must be disarmed before the entry delay expires or an will be detected.
All Burglary type zones in all areas are delayed along with the Exit zone.
Entry delay times can be from 30 to 250 seconds. Repeat the above for Entry Delay
2 if it is being used. Default is 30 seconds for Entry Delay 1.
Note: Specic Exit Error operation is based on the Entry Delay used (1 or 2) with an
EX type zone. See Exit Delay.