Installation guide
Digital Monitoring Products XT30/XT50 Programming Guide
14
remoTe oPTionS
6.7
SVC RCVR NO YES
Service Receiver Authorization
YES enables remote commands and programming to be accepted from a secondary
service receiver other than the alarm SCS-1R Receiver. The Remote Key option can
also be required.
With YES selected, the panel requests the service receiver key the rst time it is
contacted by the service receiver. The panel retains this service receiver key in
memory and accepts remote commands from the service receiver.
If an alarm occurs during a remote connect, the panel disconnects from the service
receiver and calls the alarm receiver. Alarm reports are only sent to the alarm
receiver. It is important that the alarm receiver key and the service receiver key
programmed at the central station are NOT the same so the panel can determine
the difference between receivers.
When NO is selected, remote commands and programming are not accepted from a
secondary service receiver.
6.8
DISARM NO YES
Remote Disarm
Enter YES to enable the panel to be disarmed remotely. Selecting NO disables
remote disarming.