UL 985 NFPA 72 (Chapter 2) Specications
Household Fire Warning System Units
21.1 Bell output denition
The bell output of the Model XRSuper6/XR20/XR40 must be programmed to operate steady on burglary
alarms and pulsed on re alarms. See the XRSuper6/XR20/XR40 Programming Guide (LT-0305).
21.2 Indicating Circuit Supervision
The DMP Models 865 and 866 Notication Circuit Module must be used on the bell circuit for detection of
shorts and grounds.
21.3 Wireless External Contact
When used, the External Contact of 1101, 1102, or 1103 must be programmed Normally Closed. See the
XRSuper6/XR20/XR40 Programming Guide (LT-0305).
21.4 Wireless Supervision Time
The Zone Information Supervision Time must be 3 minutes. See the XRSuper6/XR20/XR40 Programming
Guide (LT-0305).
21.5 Wireless Fire Verication
When used, the Model 1161 and 1162 wireless smoke detectors must not be programmed as Fire Verication
(FV) zone type. See the XRSuper6/XR20/XR40 Programming Guide (LT-0305).
California State Fire Marshal Specications
22.1 Bell Output Denition
The bell output of the Model XRSuper6/XR20/XR40 must be programmed to operate steady on burglary
alarms and temporal on re alarms. See the XRSuper6/XR20/XR40 Programming Guide (LT-0305).