Bell Output
7.1 Terminals 5 and 6
Nominal 12 VDC is supplied by terminal 5 on the panel to power alarm bells or horns. The output is rated
for a maximum of 1.5 Amps with a 40 VA transformer. This output can be steady, pulsed, or Temporal Code 3
depending upon the Bell Action specied in Output Options programming. Terminal 6 is the ground reference
for the bell circuit.
Keypad Data Bus
8.1 Description
Terminals 7, 8, 9, and 10 of the panel are designated as the keypad data bus. In addition to keypads,
the XRSuper6/XR20/XR40 allows the connection of any combination of zone expansion modules, 5845LX
Glassbreak Detectors, and 6155LX PIRs, to the keypad bus up to the maximum of four devices. The XRSuper6
allows the connection of four zones on address one.
8.2 Terminal 7 - RED
Nominal 12 VDC is supplied at terminal 7 to power Security Command keypads and zone expanders. This is
also where power for any auxiliary device is supplied. The ground reference for terminal 7 is terminal 10.
The maximum output is rated at 500mA. All auxiliary devices totaled together must not exceed the panel’s
maximum current rating of 500mA.
8.3 Terminal 8 - YELLOW
Data receive from keypads and zone expanders.
8.4 Terminal 9 - GREEN
Data transmit to keypads and zone expanders.
8.5 Terminal 10 - BLACK
Terminal 10 is the ground reference for Security Command keypads, zone expanders, and any auxiliary
devices being powered by terminals 7 and 11.
8.6 Programming Connection
A locking 4-pin header (J8) is provided to connect a keypad when using a DMP Model 330 Programming Cable.
This provides a quick and easy connection for programming the panel.
8.7 Keypad Addressing
Address XRSuper6
Zone #
XR20 Zone
#
XR40 Zone
#
Panel Zones 1-6 1-10 1-10
1 7-10 11-14 11-14
2 21-24 21-24 21-24
3 31-34 31-34 31-34
4 41-44 41-44 41-44
5 * * 51-54
6 N/A N/A 61-64
7 N/A N/A 71-74
8 N/A N/A 81-84
* Note: Address 5 can be used with unsupervised keypads. This allows all 16 zones to be used by Zone
Expansion Modules, such as a 714-16.
Smoke and Glassbreak Detector Output
9.1 Terminal 11
Nominal 12 VDC at 100mA maximum (shared by terminal 25) is supplied at terminal 11 to power 4-wire
smoke detectors or other auxiliary powered devices. This output can be turned off by the user for 5 seconds
using the Sensor Reset option in the User Menu. Terminal 10 is the ground reference for terminal 11.