Installation guide
Digital Monitoring Products XRSuper6/XR20/XR40 Installation Guide
6
INSTALLATION
XRSuper6/XR20/XR40 Installation Guide Digital Monitoring Products
7
INSTALLATION
6.7 XRSuper6/XR20/XR40 Standby Battery Calculations
Standby Battery Power Calculations Standby Current Alarm Current
Command Processor Panel
Active Zones 1-9 (1-5 on XRSuper6)
Active Zone 10 (Zone 6 on XRSuper6)
2-Wire Smoke Detectors
Panel Bell Output
Qty ______
Qty ______
Qty ______
x
x
x
50mA
1.6mA
4mA
0.1mA
______mA
______
______
______
Qty ______
Qty ______
Qty ______
1500mA
x
x
x
x
50mA
*2mA
30mA
0.1mA
Max.
______mA
______
______
______
______
690/690F Security Command Keypad Qty ______ x 77mA ______ Qty ______ x 84mA ______
692 Keypad Qty ______ x 30mA ______ Qty ______ x 70mA ______
693 Easy Entry Keypad Qty ______ x 92mA ______ Qty ______ x 120mA ______
790/790F Security Command Keypad
Active Zones (EOL Installed)
Qty ______ x 77mA
1.6mA
______
______
Qty ______
Qty ______
x
x
84mA
*2mA
______
______
793 Easy Entry Keypad
Active Zones (EOL Installed)
Qty ______ x 92mA
1.6mA
______
______
Qty ______
Qty ______
x
x
120mA
*2mA
______
______
770 Security Command Keypads
Active Zones (EOL Installed)
Qty ______ x 100mA
1.6mA
______
______
Qty ______
Qty ______
x
x
100mA
*2mA
______
______
7060 Thinline/7060A Aqualite Keypad Qty ______ x 72mA ______ Qty ______ x 87mA ______
7063 Thinline/7063A Aqualite Keypad Qty ______ x 85mA ______ Qty ______ x 100mA ______
7070 Thinline/7070A Aqualite Keypad
Active Zones (EOL Installed)
Qty ______ x 72mA
1.6mA
______
______
Qty ______
Qty ______
x
x
87mA
*2mA
______
______
7073 Thinline/7073A Aqualite Keypad
Active Zones (EOL Installed)
Qty ______ x 85mA
1.6mA
______
______
Qty ______
Qty ______
x
x
100mA
*2mA
______
______
7760 Clear Touch Keypad Qty ______ x 72mA ______ Qty ______ x 87mA ______
733 Wiegand Interface Module
Active Zones (EOL Installed)
Qty ______ x 30mA
1.6mA
______
______
Qty ______
Qty ______
x
x
30mA
*2mA
______
______
734 Wiegand Interface Module
Active Zones (EOL Installed)
Qty ______
Qty ______
x
x
15mA
1.6mA
______
______
Qty ______
Qty ______
x
x
15mA
*2mA
______
______
736P POPIT Interface Module
Radionics Popex, POPITs, OctoPOPITs
Qty ______
Qty ______
x
x
25mA
___mA
______
______
Qty ______
Qty ______
x
x
25mA
___mA
______
______
738A Ademco Wireless Interface Module Qty ______ x 75mA ______ Qty ______ x 75mA ______
708 Bus Extender Module (one pair) Qty ______ x 20mA ______ Qty ______ x 20mA ______
710 Bus Splitter/Repeater Module Qty ______ x 30mA ______ Qty ______ x 30mA ______
714 Zone Expansion Modules
Active Zones (EOL Installed)
Qty ______
Qty ______
x
x
7mA
1.6mA
______
______
Qty ______
Qty ______
x
x
7mA
*2mA
______
______
712-8 Zone Expansion Module
Active Zones (EOL Installed)
Qty ______
Qty ______
x
x
17mA
1.6mA
______
______
Qty ______
Qty ______
x
x
17mA
*2mA
______
______
714-8, 714-16 Zone Expansion Module
Active Zones (EOL Installed)
Qty ______
Qty ______
x
x
20mA
1.6mA
______
______
Qty ______
Qty ______
x
x
20mA
*2mA
______
______
715 Zone Expansion Module
Active Zones (EOL Installed)
2-Wire Smokes
Qty ______
Qty ______
Qty ______
x
x
x
7mA
4mA
.1mA
______
______
______
Qty ______
Qty ______
Qty ______
x
x
x
7mA
*30mA
.1mA
______
______
______
715-8, 715-16 Zone Expansion Modules
Active Zones (EOL Installed)
2-Wire Smokes
Qty ______ x 20mA
4mA
.1mA
______
______
______
Qty ______ x 20mA
*30mA
.1mA
______
______
______
iCOM
SL
Network Alarm Communicator Qty ______ 80mA ______ Qty ______ 80mA ______
FA426 16-Point Receiver 47mA ______ 47mA ______
Aux. Powered Devices on Terminals 7 and 11
Other than Keypads and Modules
______mA ______mA
Total Standby
Total Standby______mA x number of Standby Hours needed
Total Alarm
* Based on 10% of active zones in alarm condition.
______mA
______ =
______mA
+
Total
Total Alarm
________mA-hours
________mA-hours
________mA-hours
X .001
= ________Amp-hrs
______mA
Required