Installation guide

Digital Monitoring Products XRSuper6/XR20/XR40 Installation Guide
16
COMPLIANCE
19.7 Line Security for Police Connect
Basic line security is provided when the Model XRSuper6/XR20/XR40 is conÞ gured as a dialer system.
Universal UL And NFPA Fire Alarm SpeciÞ cations
20.1 Introduction
The programming and installation speciÞ cations contained in this section must be completed when installing
the Model XRSuper6/XR20/XR40 in accordance with any of the UL or NFPA Þ re standards. Additional
speciÞ cations may be required by a particular standard.
20.2 Wiring
All wiring must be in accordance with NEC, ANSI/NFPA 70.
20.3 Police station phone number
The digital dialer telephone number programmed for communication must not be a police station phone
number, unless that phone number is speciÞ cally provided for that purpose.
20.4 System maintenance
Proper installation and regular maintenance by the installing alarm company and frequent testing by the end
user is essential to ensure continuous sat isfactory operation of any alarm system. Offering a maintenance
program and acquainting the user with the correct procedure for use and testing of the system is also the
responsibility of the installing alarm company.
20.5 Audible alarm
Fire Type zones should be programmed to activate an audible alarm. The Bell Action for Fire Type zones
should not be programmed as “N.” See the XRSuper6/XR20/XR40 Programming Guide (LT-0305).
20.6 Fire zone programming
Fire zones must be programmed to activate a trouble on open conditions and an alarm on short conditions.
The swinger bypass function must not be used on any Þ re zones. See the Programming Guide (LT-0305).
20.7 Ground Start
Ground Start phone lines must not be used for UL listed systems.
20.8 UL Listed Receivers
UL has veriÞ ed operation with the DMP SCS-1/SCS-1R Security Receiver, Sur-Gard MLR2-E, SG-HLR2-DG, FBII
CP220PB, Osborne-Hoffman Quick-Alert, and Radionics D6500 receivers.
UL 985 NFPA 72 (Chapter 2) SpeciÞ cations
Household Fire Warning System Units
21.1 Bell output deÞ nition
The bell output of the Model XRSuper6/XR20/XR40 must be programmed to operate steady on burglary
alarms and pulsed on Þ re alarms. See the XRSuper6/XR20/XR40 Programming Guide (LT-0305).
21.2 Indicating Circuit Supervision
The DMP Models 865 and 866 NotiÞ cation Circuit Module must be used on the bell circuit for detection of
shorts and grounds.
California State Fire Marshal SpeciÞ cations
22.1 Bell Output DeÞ nition
The bell output of the Model XRSuper6/XR20/XR40 must be programmed to operate steady on burglary
alarms and temporal on Þ re alarms. See the XRSuper6/XR20/XR40 Programming Guide (LT-0305).