Installation guide
Digital Monitoring Products XRSuper6/XR20/XR40 Installation Guide
8
INSTALLATION
6.7 XRSuper6/XR20/XR40 Standby Battery Calculations
Standby Battery Power Calculations Standby Current Alarm Current
Command Processor Panel
Active Zones 1-9 (1-5 on XRSuper6)
Active Zone 10 (Zone 6 on XRSuper6)
2-Wire Smoke Detectors
Panel Bell Output
Qty ______x
Qty ______x
Qty ______x
50mA
1.6mA
4mA
0.1mA
______mA
______
______
______
Qty ______x
Qty ______x
Qty ______x
1500mA
50mA
*2mA
30mA
0.1mA
Max.
______mA
______
______
______
______
690/690F Security Command Keypad
Annunciator (ON)
Qty ______x 77mA ______
Qty ______x 84mA
20mA
______
______
692 Keypad Qty ______x 30mA ______ Qty ______x 70mA ______
790/790F Security Command Keypad
Active Zones (EOL Installed)
Annunciator (ON)
Qty ______x 77mA
1.6mA
______
______
Qty ______x
Qty ______x
84mA
*2mA
20mA
______
______
______
791 Easy Entry Keypad
Active Zones (EOL Installed)
Annunciator (ON)
Qty ______x 100mA
1.6mA
______
______
Qty ______x
Qty ______x
100mA
*2mA
20mA
______
______
______
693/793 Easy Entry Keypad
Active Zones (EOL Installed)
Annunciator (ON)
Qty ______x 92mA
1.6mA
______
______
Qty ______x
Qty ______x
120mA
*2mA
20mA
______
______
______
770, 771 Security Command Keypads
Active Zones (EOL Installed)
Annunciator (ON)
Qty ______x 100mA
1.6mA
______
______
Qty ______x
Qty ______x
100mA
*2mA
20mA
______
______
______
733 Wiegand Interface Module
Active Zones (EOL Installed)
Annunciator (ON)
Qty ______x 30mA
1.6mA
______
______
Qty ______x
Qty ______x
30mA
*2mA
20mA
______
______
______
736P POPIT Interface Module
Radionics Popex, POPITs, OctoPOPITs
Qty ______x
Qty ______x
25mA
___mA
______
______
Qty ______x
Qty ______x
25mA
___mA
______
______
738A Ademco Wireless Interface Module Qty ______x 75mA ______ Qty ______x 75mA ______
710 Bus Splitter/Repeater Module Qty ______x 30mA ______ Qty ______x 30mA ______
711, 771E, 714 Zone Expansion Modules
Active Zones (EOL Installed)
Qty ______x
Qty ______x
7mA
1.6mA
______
______
Qty ______x
Qty ______x
7mA
*2mA
______
______
712-8 Zone Expansion Module
Active Zones (EOL Installed)
Qty ______x
Qty ______x
17mA
1.6mA
______
______
Qty ______x
Qty ______x
17mA
*2mA
______
______
714-8, 714-16 Zone Expansion Module
Active Zones (EOL Installed)
Qty ______x
Qty ______x
20mA
1.6mA
______
______
Qty ______x
Qty ______x
20mA
*2mA
______
______
715 Zone Expansion Module
Active Zones (EOL Installed)
2-Wire Smokes
Qty ______x
Qty ______x
Qty ______x
7mA
4mA
.1mA
______
______
______
Qty ______x
Qty ______x
Qty ______x
7mA
*30mA
.1mA
______
______
______
715-8, 715-16 Zone Expansion Modules
Active Zones (EOL Installed)
2-Wire Smokes
Qty ______x 20mA
4mA
.1mA
______
______
______
Qty ______x 20mA
*30mA
.1mA
______
______
______
iCOM
SL
Internet Alarm Communicator 80mA ______ 80mA ______
FA426 16-Point Receiver 47mA ______ 47mA ______
Aux. Powered Devices on Terminals 7 and 11
Other than Keypads and Modules
______mA ______mA
Total Standby
Total Standby______mA x number of Standby Hours needed
Total Alarm
* Based on 10% of active zones in alarm condition.
______mA
______ =
______mA
+
Total
Total Alarm
________mA-hours
________mA-hours
________mA-hours
X .0001
= ________Amp-hrs
______mA
Required