Installation guide
Digital Monitoring Products  XRSuper6/XR20/XR40 Installation Guide
4
INTRODUCTION
3.5 XRSuper6/XR20/XR40 Wiring Diagram
J4
RED
PROG
J8
XR20/XR40 
Command 
Processorâ„¢ Panel
J16 
Command 
Processor Reset
J7
RJ SUP
AC
1
2
3
456 7
8
10
11 12 13 14
15
16 17 18
19
9
20
21
22 23
24
25
26
+B
BELL
GND
SMK
RED
YEL
GRN
BLK
Z1
Z2 Z3 Z4
Z5
Z6
Z7
Z8 Z9
Z10-
AC
-B
GND
GND
GND
GND
Z10+
s s
1k 
Ohm
Zone 1
s s
1k 
Ohm
Zone 2
s s
1k 
Ohm
Zone 3
s s
1k 
Ohm
Zone 4
s s
1k 
Ohm
Zone 5
s s
1k 
Ohm
Zone 6
s s
1k 
Ohm
Zone 7
1k Ohm
Zone 8
s
1k Ohm
Zone 9 
s s
Programmer Header J8 
Use DMP Model 330 Harness
RJ Cable Monitor J7 
Use DMP Model 306 Harness
Phone Jack Connector
See XRSuper6 detail below
Front 
Tamper
Plug 
into 
120 
16 to 18 
gauge wire
Maximum AC Wire distance 
with 16 gauge wire: 70 feet
with 18 gauge wire: 40 feet
RED
BLACK
Cold Water Pipe 
Earth Ground 
Bell
Zone Expander 
Model 715 
7mA @ 12 VDC
Models 715-8, 715-16
20mA @ 12 VDC
Smoke 
Detector
3.3k Ohm
s
= Supervised Circuit
Smoke Output
100mA @10.4 - 13.2 VDC
Terminal 11 
22 gauge minimum
22 gauge minimum
22 gauge minimum
22 gauge minimum
RED
YELLOW
GREEN
BLACK
Zone Expander 
Model 714
7mA @ 12 VDC
Models 714-8, 714-16
20mA @ 12 VDC
s
s
s s s s
s
Rear 
Tamper
s
AC Wiring must be in conduit and exit out 
the left side of the enclosure. 
Wiring on terminals 5 through 22 must exit 
right and maintain a 1/4" separation from 
the AC and battery positive wiring. 
POWER
ARMED
RED
BLACK
Use UL Listed 
Power Supervision 
Relay rated at 12 
VDC.
The Class 2, Class 3, and power-limited fire alarm circuits are installed using 
CL#, CL3R, or CL3P, or substitute cable permitted by the National Electric 
code, ANSI/NFPA 70. The Class 2, Class 3, and power-limited fire alarm 
circuit conductors extedning beyond the cable jacket are separated a 
minimum of 1/4 in. or by nonconductive tubing or by a nonconductive barrier.
DMP Transformers
Model 320
16.5 VAC 40 VA 
Class 2 wire-in.
Model 321
16.5 VAC 40 VA 
Class 2 plug-in.
Model 324
16.5 VAC 20 VA
Class 2 plug-in. 
Secondary Power Supply
1.2 Amps max. charging 
current. Use only 12 VDC 
rechargeable batteries. DMP 
Model 367. Replace every 3 to 5 
years.
Bell
10.4 - 13.2 VDC
T
otal current:
1.5 Amps max. w/ 40 VA
600mA w/ 20 VA
Household System
A
n alarm sounding device must 
be installed indoors so that it is 
clearly heard in all sleeping 
areas.
Keypads
Model 690/690F
72mA @ 8 - 14.5 VDC
Models 790/790F and 791
75mA @ 8 - 14.5 VDC
Models 770 and 771
100mA @ 8 - 16 VDC
Model 693/793
108mA @ 8 - 14.5 VDC
Model 692
70mA @ 8 -16 VDC
Tamper protection 
when required for 
Model 350A Attack 
Resistant Enclosure.
Heat detectors, 
manual pull 
stations, or any 
other shorting 
device. Unlimited 
number of units.
Zone 6 compatibility 
identifier: A
Maximum operating 
range: 8.8 VDC - 
14.2 VDC.
See the list of approved 2-wire smoke 
detectors in Section 11.1 of the 
Installation Guide. 
UL Listed Resistors
1.0k Ohm - DMP Model 311
3.3k Ohm - DMP Model 309
10K Ohm - DMP Model 308 
15
16 17 18
25
26
Z3 Z4
Z5
Z6-
GND
Z6+
3.3K EOL1K EOL 1K EOL
1K EOL
XRSuper6
Detail for XRSuper6
Figure 1: System Wiring Diagram










