Installation guide

Digital Monitoring Products XRSuper6/XR20/XR40 Installation Guide
4
INTRODUCTION
3.5 XRSuper6/XR20/XR40 Wiring Diagram
J4
RED
PROG
J8
XR20/XR40
Command
Processorâ„¢ Panel
J16
Command
Processor Reset
J7
RJ SUP
AC
1
2
3
456 7
8
10
11 12 13 14
15
16 17 18
19
9
20
21
22 23
24
25
26
+B
BELL
GND
SMK
RED
YEL
GRN
BLK
Z1
Z2 Z3 Z4
Z5
Z6
Z7
Z8 Z9
Z10-
AC
-B
GND
GND
GND
GND
Z10+
s s
1k
Ohm
Zone 1
s s
1k
Ohm
Zone 2
s s
1k
Ohm
Zone 3
s s
1k
Ohm
Zone 4
s s
1k
Ohm
Zone 5
s s
1k
Ohm
Zone 6
s s
1k
Ohm
Zone 7
1k Ohm
Zone 8
s
1k Ohm
Zone 9
s s
Programmer Header J8
Use DMP Model 330 Harness
RJ Cable Monitor J7
Use DMP Model 306 Harness
Phone Jack Connector
See XRSuper6 detail below
Front
Tamper
Plug
into
120
16 to 18
gauge wire
Maximum AC Wire distance
with 16 gauge wire: 70 feet
with 18 gauge wire: 40 feet
RED
BLACK
Cold Water Pipe
Earth Ground
Bell
Zone Expander
Model 715
7mA @ 12 VDC
Models 715-8, 715-16
20mA @ 12 VDC
Smoke
Detector
3.3k Ohm
s
= Supervised Circuit
Smoke Output
100mA @10.4 - 13.2 VDC
Terminal 11
22 gauge minimum
22 gauge minimum
22 gauge minimum
22 gauge minimum
RED
YELLOW
GREEN
BLACK
Zone Expander
Model 714
7mA @ 12 VDC
Models 714-8, 714-16
20mA @ 12 VDC
s
s
s s s s
s
Rear
Tamper
s
AC Wiring must be in conduit and exit out
the left side of the enclosure.
Wiring on terminals 5 through 22 must exit
right and maintain a 1/4" separation from
the AC and battery positive wiring.
POWER
ARMED
RED
BLACK
Use UL Listed
Power Supervision
Relay rated at 12
VDC.
The Class 2, Class 3, and power-limited fire alarm circuits are installed using
CL#, CL3R, or CL3P, or substitute cable permitted by the National Electric
code, ANSI/NFPA 70. The Class 2, Class 3, and power-limited fire alarm
circuit conductors extedning beyond the cable jacket are separated a
minimum of 1/4 in. or by nonconductive tubing or by a nonconductive barrier.
DMP Transformers
Model 320
16.5 VAC 40 VA
Class 2 wire-in.
Model 321
16.5 VAC 40 VA
Class 2 plug-in.
Model 324
16.5 VAC 20 VA
Class 2 plug-in.
Secondary Power Supply
1.2 Amps max. charging
current. Use only 12 VDC
rechargeable batteries. DMP
Model 367. Replace every 3 to 5
years.
Bell
10.4 - 13.2 VDC
T
otal current:
1.5 Amps max. w/ 40 VA
600mA w/ 20 VA
Household System
A
n alarm sounding device must
be installed indoors so that it is
clearly heard in all sleeping
areas.
Keypads
Model 690/690F
72mA @ 8 - 14.5 VDC
Models 790/790F and 791
75mA @ 8 - 14.5 VDC
Models 770 and 771
100mA @ 8 - 16 VDC
Model 693/793
108mA @ 8 - 14.5 VDC
Model 692
70mA @ 8 -16 VDC
Tamper protection
when required for
Model 350A Attack
Resistant Enclosure.
Heat detectors,
manual pull
stations, or any
other shorting
device. Unlimited
number of units.
Zone 6 compatibility
identifier: A
Maximum operating
range: 8.8 VDC -
14.2 VDC.
See the list of approved 2-wire smoke
detectors in Section 11.1 of the
Installation Guide.
UL Listed Resistors
1.0k Ohm - DMP Model 311
3.3k Ohm - DMP Model 309
10K Ohm - DMP Model 308
15
16 17 18
25
26
Z3 Z4
Z5
Z6-
GND
Z6+
3.3K EOL1K EOL 1K EOL
1K EOL
XRSuper6
Detail for XRSuper6
Figure 1: System Wiring Diagram