User`s guide

28 XR200-485 User Menu
Setting Output (OUT) and Door (DOOR) Schedules
The Schedules function allows you to set up to 100 different
scheduled times for relay outputs and door access relays connected
to your system to turn ON and OFF automatically. The maximum
number of schedules that can be assigned per door access relay
or relay output is 8.
1. Access the User Menu.
2. Press COMMAND until SCHEDULES? displays.
3. After you have accessed the SCHEDULES? menu and the
schedule options, S1 S2 S3 S4, have been displayed, press
the COMMAND key once more and the display will change to
OUT DOOR HOL EXT. Press the Select key under OUT or
DOOR.
4. At the OUTPUT NO: – or DOOR NO: – display, enter the output
number you want to program. Press the COMMAND key.
If adding a schedule and all 100 are currently in use, you will get an
OUT SCHEDS FULL display. You must then delete an existing
schedule.
5. The keypad displays SCHEDULE NO: -. Enter the schedule
number (1 to 8) and press the COMMAND key.
6. The keypad displays SUN MON TUE WED. Press the COMMAND
key to display THU FRI SAT HOL.
7. Press the Select key under the day you want to program. If
you select HOL go to Setting Holiday ABC Schedules for more
information.
Note: After Selecting the day of the week for the schedule to
occur, the keypad displays any currently programmed ON OFF
times previously set for that day. This feature allows you to review
programmed schedules at any time.
8. If ON OFF times are displayed, the keypad then displays
DELETE KEEP. Press the Select key under DELETE to enter
new times.
9. The keypad then displays ON TIME?. This is followed by the
display – : AM PM.
Enter a new relay ON time and Select AM or PM.
The display changes to OFF TIME?. This is followed by the
display – : AM PM.
Enter a new OFF time for the relay.
Enter all schedule times using a 12 hour clock. For example,
to enter 6 AM you would enter a 0 + 6 + 0 + 0 and press the
Select key under AM. For 11 PM you would enter a 1 + 1 + 0
+ 0 and press the Select key under PM.
10. The keypad returns to the day of the week display allowing you
to enter another Output or Door schedule. To exit the user
menu or to go back to the S1 S2 S3 S4 display, press the Back
Arrow key.
11. To clear a schedule press DELETE and then AM when the
opening time is requested.