Programming instructions
28
XR200 Programming Guide
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
How it works
If a zone trips the total number of times specified in section 7.7 within one hour, the panel
bypasses it until either the area in which the zone is assigned is disarmed, the zone is
manually reset through the Bypass Zones? keypad User Menu function, or the zone remains
normal for one hour and the Reset Swinger Bypass is YES. See section 7.8.
If the zone trips fewer than the specified times within one hour, the bypass trip counter
returns to zero and the process must be repeated.
A report of the swinger bypass is sent to the receiver if Bypass Reports is YES. See section
6.4.
13.11 FAST RESPONSE
Select YES to provide a zone response time of 167ms. Select NO to provide a normal zone
response time of 500ms. Zones 100 to 299 have a fixed response time of 200ms and do not
display this prompt.
13.12 CROSS ZONE
Select YES to enable cross zoning for this zone. Cross zoning requires one or more armed
zones to fault within a programmed time before an alarm report is sent to the receiver.
When a cross zoned zone trips, the bell action assigned to the zone activates. The cross
zone time specified in section 7.4, System Options, begins to count down. If another cross
zoned zone in the same area faults, or if the first zone restores and faults again before a
Sensor Reset is done , the panel sends an alarm report.
If no other cross zoned zone in the same area trips before the cross zone time expires, the
panel sends only a zone fault report to the receiver.
Cross zoning is not compatible with all zone types:
You cannot enable cross zoning for Fire verify zones or for
any Fire zone type that has Retard Delay set to YES.
13.13 PRIORITY
Select YES to provide additional protection for the premises by requiring this zone to be in a
normal condition before its assigned area can be armed.
ZONE NUMBER - Enter the zone number to program next. Return to section 13.2 and follow
the descriptions of each programming prompt. If all zones are programmed, press the
ARROW key at the ZONE NO: – display to continue.
Note:
If you programmed any wireless zones, press the ARROW key for the following wireless programming.
13.13A PROGRAM TRANSMITTER
Select YES to program wireless transmitters. Select NO to return to ZONE INFORMATION.
13.13B CONNECT TRANSMITTER
Connect the transmitter, whose zone number is displayed, to the Programming Connector on
the 472 H
ARD-WIRE-LESS Card using the 620 Programming Cable. RESET THE
TRANSMITTER. The keypad display prompts you for transmitters starting from the lowest
zone number to the highest.
At the CONNECT XMTR: prompt, you can also press a SELECT key and enter in any
wireless zone number (100 to 299 or 000 for the C100 and FA100 transmitters). After
programming all transmitters, press the COMMAND key.
13.13C CONNECT COMMAND TRANSMITTER
Connect the C100 or FA100 you want assigned to the partition shown (P1 = Partition 1) to
the 472 Card. Press the Alert button on the transmitter to initiate programming. Repeat the
programming for each partition. To use the Alert button on the transmitter as a panic,
program AMBUSH as YES in System Reports.
13 - ZONE INFORMATION
FAST RSP NO
CRS ZONE NO
PRIORITY NO
ZONE NO: –
CONNECT C100 P 1
PRG XMTR? NO YES
CONNECT XMTR: ***