13.1 ZONE INFORMATION
Zone Information allows you to define the operation of each protection zone used in the
system. All protection zones, whether located on a command processor panel, Security
Command keypad, or zone expander are programmed the same way.
A description of each specification follows:
13.2 ZONE NUMBER
Enter the number of the zone you intend to program. Press COMMAND to enter a zone
name. For instructions on entering alphanumeric characters, see section 1.7.
13.3 ZONE NAME
Zone names can have up to 16 alphanumeric characters. A name must be given to each
zone in the system. The name can display at the keypads during arming and disarming so
the user does not have to memorize zone numbers. Users can associate a zone name with a
particular protection point. A zone that is not part of the system must be marked unused.
To add a zone name to the system, press any SELECT key and then enter up to 16
characters for the new zone name. Press COMMAND to continue.
To mark a zone unused, delete the old name by pressing a top row SELECT key, then press
the COMMAND key. The programmer automatically programs the name as * UNUSED *. If
you have already cleared Zone Information during Initialization, the zones will be marked *
UNUSED *. See section 2.5.
13.4 ZONE TYPE
The Zone Type defines the panel's response to the zone being opened or shorted. This is
called the Alarm Action. There are up to 13 possible alarm action responses depending on
the zone type and any restrictions it may have. See the chart in section 13.6.
When you assign a Zone Type to a zone, responses are made automatically for the zone.
There are 12 Zone Types to choose from. Application descriptions for each zone type can be
found in the Appendix section of this manual.
To enter a new Zone Type, press any SELECT key. The display lists all of the available
Zone Types four at a time.
Blank, Night, Day, or Exit. Press COMMAND for additional zone types.
Fire, Panic, Emergency, or Supervisory. Press COMMAND for additional zone types.
Auxiliary 1, Auxiliary 2, Fire Verify, or Arming (keyswitch). Press the ARROW key to display
the previous zone types. When the Zone Type you want is displayed, press the SELECT key
beneath it.
If you select Blank, Night, Day, Exit, Auxiliary 1, Auxiliary 2, or Arming as the Zone Type, the
zone must be assigned to an active area. If you select Fire, Fire Verify, Panic, Emergency, or
Supervisory as the Zone Type, it's a 24 hour zone that is always armed and no area
assignment is needed.
Zone Type Specifications
The XR200 contains 12 default zone types for use in configuring the system. These zone
types provide the most commonly selected functions for their applications. All zone types
except the Arming zone type can be customized by changing the options listed below.
Refer to section 16.6 in the Appendix for complete zone type descriptions.
13 - ZONE INFORMATION
ZONE NO: -
ZONE INFORMATION
ZONE TYPE: BLANK
* UNUSED *
– – NT DY EX
A1 A2 FV AR
F I PN EM SV