Programming instructions
17
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
XR200 Programming Guide
8.5D FIRE ALARM OUTPUT
Enter output number to turn on when a fire type zone is placed in alarm. The output is turned
off using the Sensor Reset option while no additional fire type zones are in alarm.
Enter zero
to disable this output.
This output is not compatible with Cutoff Outputs (8.5A).
8.5E FIRE TROUBLE OUTPUT
Enter output number to turn on when a fire type zone is placed in trouble or when a
supervisory type zone is placed in alarm or trouble. The output is turned off when all fire and
supervisory type zones are restored to normal.
Enter zero to disable this output.
This output
is not compatible with Cutoff Outputs (8.5A).
8.5F AMBUSH OUTPUT
Enter output number to turn on when an Ambush code is entered at a keypad. The output is
turned off using the Sensor Reset option.
Enter zero to disable this output.
8.5G ENTRY OUTPUT
Enter output number to turn on at the start of the entry delay time. The output is turned off
when the area is disarmed or the entry delay time expires. Enter zero to disable this output.
8.5H EXIT OUTPUT
Enter output number to turn on when an exit delay time starts in any area of the system. The
output is turned off when the area arms or when the arming has been stopped. Enter zero to
disable this output.
8.5I READY OUTPUT
Enter output number to turn on when all disarmed burglary zone types are in a normal state.
The output is turned off when any disarmed burglary type zone is in a bad state. Enter zero
to disable this output. This output is not compatible with Cutoff Outputs (8.5A).
8.5J PHONE TROUBLE OUTPUT
Enter output number to turn on when the phone line monitor in the DMP 893 or 893A Dual
Phone Line Module detects a voltage below 3 VDC. The output is turned off when phone
voltage rises above 3 VDC. Enter zero to disable this output.
8.5K LATE TO CLOSE OUTPUT
Enter the output number to turn on at the expiration of a Closing schedule. The output
activates simultaneously with the CLOSING TIME! keypad display. The output is turned off
when the area is armed, the Closing is extended, or the schedule is changed.
8.5L DEVICE FAIL OUTPUT
Enter output number to turn on when an addressed device fails to respond to polling from the
panel. A Missing Device report is also sent to the receiver. The output is turned off when the
device responds to polling or is removed from the system.
Enter zero to disable this output
and LX-Bus™ device fail reporting to the receiver.
Any Output Option can be used with output numbers 1 through 10 and 100 through 299.
8 - OUTPUT OPTIONS
READY OUT: 0
LATE CLS OUT: 0
PH TRBL OUT: 0
DVC FAIL OUT: 0
ENTRY OUT: 0
EXIT OUT: 0
FIRE ALR OUT: 0
FIRE TRB OUT: 0
AMBUSH OUT: 0