Programming instructions

16
XR200 Programming Guide
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
8.4 BELL ACTION
This section allows you to define the type of Bell Output for zone alarms. (Trouble conditions
do not activate the Bell Output.) Press COMMAND to display the default Bell Output for each
zone type. To change the output, press any SELECT key and enter S to provide a Steady Bell
Output, P for a Pulsed output. T for a Temporal Code 3 output, and N for no Bell Output.
8.4A FIRE BELL ACTION
Defines Bell Action for Fire Type zones. The default is set at P.
8.4B BURGLARY BELL ACTION
Defines Bell Action for Burglary Type zones and Exit Error output. The default is set at S.
8.4C SUPERVISORY BELL ACTION
Defines Bell Action for Supervisory Type zones. The default is set at N.
8.4D PANIC BELL ACTION
Defines Bell Action for Panic Type zones. The default is set at N.
8.4E EMERGENCY BELL ACTION
Defines Bell Action for Emergency Type zones. The default is set at N.
8.4F AUXILIARY 1 BELL ACTION
Defines Bell Action for Auxiliary 1 Type zones. The default is set at N.
8.4G AUXILIARY 2 BELL ACTION
Defines Bell Action for Auxiliary 2 Type zones. The default is set at N.
8.5 OUTPUT ACTION
This option allows you to define the operation of the XR200 relay outputs. The panel provides
two Form C relays (1 and 2) and eight 12 VDC voltage outputs (3 to 10) rated at 50mA each.
You can expand the system to 200 additional relay outputs (numbered 100 to 299) using
multiple 716 Output Expander Modules and at least two expansion interface cards. If the
Model 485 is used keypad door strike relays can be programmed by entering D1 - D16 for
addresses 1 -16.
8.5A CUTOFF OUTPUT
Outputs 1 to 8 can be entered here to turn off after a time specified in CUTOFF TIME. See
section 8.5B. To disable this option, press any SELECT key to clear the display then press
COMMAND. The Cutoff Output displays NONE when no outputs are selected.
8.5B OUTPUT CUTOFF TIME
If a Cutoff Output is assigned in section 8.5A, you can enter a Cutoff Time of 1 to 99 minutes
(in one minute increments) for the output to remain on.
Enter zero for continuous output.
8.5C COMMUNICATION FAILURE OUTPUT
Enter output number to turn on when any of the following conditions occur:
a DD system fails to communicate on three successive dial attempts
a MPX system does not communicate with the receiver for 150 seconds or if the backup
communication line transmits a report
Enter zero to disable this output.
8 - OUTPUT OPTIONS
BELL ACTION . . . . .
FIRE TYPE: P
EMERGNCY TYPE: N
AUXLRY I TYPE: N
AUXLRY 2 TYPE: N
COM FAIL OUT: 0
CO OUTS: - - - - - -
CUTOFF TIME: 0
OUTPUT ACTION . . .
SUPRVSRY TYPE: N
BURGLARY TYPE: S
PANIC TYPE: N