7.6 POWER FAIL DELAY
This option tracks the duration of an AC power failure. When the AC power is off for the
length of the programmed delay time, an AC power failure report is sent to the receiver. The
delay time can be from 1 to 9 hours. Entering a zero sends the AC power failure report after a
15 second delay.
7.7 SWINGER BYPASS TRIPS
Enter the number of times a zone can go into an alarm or trouble condition within one hour
before being automatically bypassed. You can select from 1 to 7 trips. Bypassed zones are
automatically reset when the area they're assigned to is disarmed. All 24 hour zones are
reset when any area of the system is disarmed. Entering a zero disables this function.
How it works
The panel's hour timer starts at 59 minutes past the hour. If the hour timer expires before the
trip counter is exceeded, the trip counter returns to zero. If the trip counter is exceeded
before the hour expires, the zone is automatically bypassed by the panel. A report of the
automatic bypass is sent to the receiver if Bypass Reports has been selected as YES. See
section 6.4.
7.8 RESET SWINGER BYPASS
When YES is selected, an automatically bypassed zone is reset if it remains in a normal
condition for one complete hour after being bypassed. A report of the automatic reset is sent
to the receiver if Bypass Reports has been selected as YES. See section 6.4.
7.9 VIDEO/ALARM VERIFICATION
Selecting YES forces the panel to wait for 60 seconds after a successful communication with
a central station receiver before making any additional communication attempts. This 60
second period can be used to allow video transmission or alarm verification (such as 2-way
voice) equipment to use the phone line. After the 60 second timer, the panel can once again
seize the phone line and send any reports being buffered.
The Video option must be set to NO if any fire protection is connected to the XR200.
8.1 OUTPUT OPTIONS
This function allows you to program the panel's Bell Output functions and certain Relay
Output options. Dry contact relays and voltage outputs are available using the output harness
on the XR200 board. Refer to the XR200 Installation Guide (LT-0169) for complete
information. A description of each output option follows:
8.2 BELL CUTOFF TIME
Enter the maximum time the Bell Output remains on. If the Bell Output is manually silenced
or the area is disarmed, the cutoff time is reset. The Bell Cutoff Time can be from 1 to 99
minutes. Enter zero to provide continuous bell output.
8.3 AUTOMATIC BELL TEST
When YES is selected, the Bell Output is turned on for two seconds each time a partition is
completely armed from a keypad. This test is delayed until the Closing Wait acknowledge is
received (if selected). See section 7.2. The Bell Test only occurs when the areas are armed
from a keypad. Arming performed from an Arming zone or remotely from Remote Access™
does not activate the Bell Test.
7 - SYSTEM OPTIONS
RST SBYP YES
BELL CUTOFF: 15
PWR FAIL HRS: 1
OUTPUT OPTIONS
BELL TST NO
VIDEO NO
8 - OUTPUT OPTIONS
SWGRBYPS TRIPS: 3