Programming instructions
11
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282
XR200 Programming Guide
4.3 DEVICE TYPE
This prompt allows you to specify that a device is installed at a particular address on the
keypad bus.
STANDARD - The device is either a Security Command keypad, a 711, 714, or 715 Zone
Expander, a 6155LX PIR, DS775LX PIR, 5845LX Glassbreak Detector, or a 733 Wiegand
Interface Module.
NONE - No device is set for this address.
If you entered 2, 3, or 4 in section 4.2 MAX PARTITION, the keypad displays the
PARTITION NO: prompt. If there is only one partition programmed in section 4.2, the keypad
does not display the partition assignment prompt.
4.4 PARTITION NUMBER
Enter the partition number where the current device being programmed is assigned. For
systems with more than one partition, press any top row SELECT key then enter a 1, 2, 3, or
4. Press COMMAND to program the next device.
Note: Programming options 4.5 - 4.8 only appear if the Model 485 Access Control Expansion
card is used.
4.5 ACCESS AREAS
Enter the area numbers (1 to 8 for partition 1 and 1 to 4 for partitions 2, 3, & 4). Users must
have matching access area numbers assigned to their code, to receive a door access at this
device.
If you do not enter any area numbers, all users with Door Access authority will receive a door
access without regard to schedules. If the user code is programmed for Anti-Pass YES, then
the user will be logged into all matching areas. This user will not be allowed to access these
areas again until they have egressed the area. See Section 4.6.
4.6 EGRESS AREAS
Use this option to detect Anti-passback violations. Enter the area numbers (1 to 8 for partition
1 and 1 to 4 for partitions 2, 3, & 4). Users must have matching access area numbers
assigned to their code, to receive a door access at this device. If the user is programmed for
Anti-Pass YES, then the user will be logged out of all matching areas. This will allow the user
to again access the area. See Section 4.5.
If you do not enter any area numbers, all users with Door Access authority will receive a door
access without regard to schedules. If you are not using the Anti-Pass feature leave the
option blank.
4.7 STRIKE TIME
This prompt allows you to enter a door access time during which a keypad or access control
device relay will be activated. Magnetic locks or electric door strikes can be connected to the
relay and released for the length of time specified here.
Enter a time between 1 and 250 seconds. The default is 5 seconds.
4.8 FIRE EXIT RELEASE
Select YES to allow the door access relay at this address to be released whenever Fire panic
keys are pressed or a Fire or Fire Verify zone alarm is in the Status List. The relay is reset
whenever a Sensor Reset is performed to remove all Fire and Fire Verify zone alarms from
the Status List.
Select NO to not allow the door access relay at this address to be released.
4 - DEVICE SETUP
DEVICE 1: STNDRD
STD NONE
PARTITION NO: 1
ACCESS - - - - - - - -
EGRESS - - - - - - - -
STRIKE TIME: 5
FIRE EXIT NO