Installation guide
Digital Monitoring Products XR200 Installation Guide
20
WIRING DIAGRAMS
XR200 Installation Guide Digital Monitoring Products
21
WIRING DIAGRAMS
20.3 Multiple Notication Circuit Modules for Zoned Annunciation
AC
1
2
3
4 5 6 7
8
10
11 12 13 14
15
16 17 18
19
9
20
21
22 23
24
25
26 27
28
+B
BELL
GND
SMK
GND
RED
YEL
GRN
BLK
Z1
Z2 Z3 Z4
Z5
Z6
Z7
Z8 Z9+
Z9-
Z10+
Z10-
AC
-B
GND
GND
GND
GND
XR200 Command Processor™ Panel
J3
DD, MPX
Selection
Headers
J4
Tamper
Header
J2 Output Header
All outputs must be located
within the same room as
the control panel.
J10
J16
Panel
Reset
J11J12
J6 Interface Card Connector
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble
866 Module
Normal/Silence Switch
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In +
5 Bell PWR In -
6 Bell Out A +
10 Bell Trouble
11 Bell Trouble
865 Module
Normal/Silence Switch
10K EOL
DMP Model 308
UL Listed,
Polarized
Notification
Appliances
Style W
UL Listed,
Polarized
Notification
Appliances
Style y
24 VDC �
5 Amp
Maximum
Power Supply Trouble
Contacts N/C
7 Bell Out A -
8 Bell Out B +
9 Bell Out B -
504-24
Power
Supply
+ -
Zone 1 Notification
Circuit Module
DMP Model 866
45mA @ 12 VDC
1K EOL
+
-
+
-
Auxiliary Power Supply must be
regulated, UL Listed for Fire Protective
Signaling Service. Power Supplies must
have battery backup.
S
S
S
S
S
S
S
S
S
S
S
S
To additional Zone 1 Notification Circuit
Modules.
Install up to a maximum of twenty-five
866 Modules by using the relay outputs
available on the XR200 panel.
All modules must be installed in a
340FC, 349, or 350 Enclosure connected
by no more than 20 feet of conduit.
Zone 2 Notification
Circuit Module
DMP Model 865
26mA @ 12 VDC
The Auxiliary Power Supply and
Notification Circuit Module trouble
contact zone must be programmed as
a Supervisory Type zone and must be
selected for display in the keypad
status list (See Status List section in
the Programming Guide (LT-0196)).
Note: If an auxiliary power supply is
not used, terminals 3 and 4 can be
jumpered together to supply Bell
Power from the XR200 panel.
A maximum of 1.5 Amps as 12 VDC is
available from terminal 5 of the
XR200 panel.
10K EOL
DMP Model 308
UL Listed,
Polarized
Notification
Appliances
Style W
24 VDC 5
Amp
Maximum
Power Supply Trouble
Contacts N/C
24 VDC �
5 Amp
Maximum
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble
866 Module
Normal/Silence Switch
Common Notification
Circuit Module
DMP Model 866
45mA @ 12 VDC
1K EOL
504-24
Power
Supply
+ -
S
S
S
S
S
S
504-24
Power
Supply
+ -
S
S
S
To additional notification
circuit modules.
Each 866 Notification Appliance
Circuit Module in alarm draws up to
30mA through its Terminal 3 Alarm
Input and 45mA from its Terminal 1
Aux Power Input.
Each 865 Notification Appliance
Circuit Module in alarm draws up to
59mA through its Terminal 3 Alarm
Input and 26mA from its Terminal 1
Aux Power Input.
S
= Supervised Circuit
K2 K4
K6 K7
Relay Output 1
Use Model 305
Relay Output 2
Use Model 305
Answering Machine
Bypass Relay
Use Model 305
Ground Start Relay
Use Model 305
Zone 1 Output
Relay 1
N/O
Orange
Zone 2 Output
Relay 1
N/O
Orange
Relay 1 and 2
Common
Gray
Outputs 3 through 10
can switch up to
50mA each at 12
VDC. This is
sufficient for one 866
Module per indicating
zone 3 through 10.