Installation guide

Digital Monitoring Products XR200 Installation Guide
18
COMPLIANCE
XR200 Installation Guide Digital Monitoring Products
19
WIRING DIAGRAMS
18.7 Local Protective Signaling Systems
The DMP Model 865, 866, or 867 Notication Circuit Module must be used on the bell circuit for detection
of shorts and grounds. See sections 25.1 to 25.3 for wiring diagrams. Model 770 series keypads that are used
to display troubles for local re alarm systems must be installed within a DMP Model 777 Keypad Protector.
Model 790 series keypads that are used to display troubles for local re alarm systems must be installed
within a DMP Model 777 with 777S 1.0” spacer. Any burglary or other off premises communication must
be done with the Model 893 Dual Phone Line Module. For local commercial re installations, the 893 is
required.
18.8 Proprietary Protective Signaling Systems
The total number of panels assigned to one MPX receiving line of the DMP SCS-1 Receiver system must not
exceed 90. This may be increased to 180 by setting the SNRM option to NO in the SCS-1 Receiver system. This
is to allow any report from a XR200 to be sent to the receiver within 90 seconds.
18.9 Remote Station Protective Signaling Systems
You must provide 60 hours of standby battery. Up to four 12 VDC, 6.5 Ah batteries may be used. See
section 6.6 for standby battery calculations. Two Radionics Model D127 Reversing Relay Modules provide
two reversing polarity telephone connections. See section 25.5 and the D127 Installation Instruction sheet
for wiring details. A DMP Model 893 is used to provide two line dialer communication or Type 1 Multiplex
communication.
18.10 Fire Protective Signaling Systems with an iCOM™
The XR200 Command Processor™ Panel must be programmed as described below for Fire Protective Signaling
Systems using an iCOM™ Internet Alarm Router for communication.
UL AA must be programmed as NO
SUB CODE must be programmed as YES
CHECKIN must be programmed as 1
RETRY TIME must be programmed as 1
FAIL TIME must be programmed as 1
NET TRBL must be programmed as YES
Refer to the iCOM™ Internet Alarm Router Installation Sheet (LT-0587) for more information.
California State Fire Marshal Specications
19.1 Bell Output Denition
The Bell Output of the XR200 panel must be programmed to operate steady on burglary alarms and pulsed,
temporal, or California School Code on re alarms. See sections 8.4.1 and 8.4.2 of the XR200 Programming
Guide (LT-0196).