Installation guide

Digital Monitoring Products XR200 Installation Guide
16
COMPLIANCE
XR200 Installation Guide Digital Monitoring Products
17
COMPLIANCE
Universal UL And NFPA Fire Alarm Specications
16.1 Introduction
The programming and installation specications contained in this section must be completed when installing
the Model XR200 in accordance with any of the UL or NFPA re standards. Additional specications may be
required by a particular standard.
16.2 Wiring
All wiring must be in accordance with NEC, ANSI/NFPA 70.
16.3 Transformer
A wire-in transformer should be used. Use the 16.5 VAC 40 VA DMP Model 320. The transformer must be
mounted within 20 feet of the panel connected by conduit.
16.4 End-of-Line Resistor
The DMP Model 310 1K Ohm EOL resistor should be used on all 1K Ohm EOL re zones.
16.5 System Trouble Display
The Status List Display must include at least one keypad that displays system monitor troubles. See section
10.3 of the XR200 Programming Guide (LT-0196).
16.6 Fire Display
The Status List Display must include at least one keypad that displays troubles and alarms on re type zones.
See section 10.4 of the XR200 Programming Guide (LT-0196).
16.7 Police Station Phone Number
The digital dialer telephone number programmed for communication must not be a police station phone
number, unless that phone number is specically provided for that purpose.
16.8 System Maintenance
Proper installation and regular maintenance by the installing alarm company and frequent testing by the end
user is essential to ensure continuous satisfactory operation of any alarm system. Offering a maintenance
program and acquainting the user with the correct procedure for use and testing of the system is also the
responsibility of the installing alarm company.
16.9 Audible Alarm
Fire Type zones should be programmed to activate an audible alarm. The Bell Action for Fire Type zones
should not be programmed as “N”. See section 8.4.1 in the XR200 Programming Guide (LT-0196).
16.10 Fire Zone Programming
If a retard delay is used on a waterow zone, it cannot exceed 90 seconds and any retard delay in the
waterow initiating devices must be subtracted from the 90 seconds allowed. See sections 13.4 and 13.17
in the XR200 Programming Guide (LT-0196). The retard delay should not be used on a zone with smoke
detectors.
16.11 Style D Zones
If required, the DMP 869 Dual Style D Initiating Module provides for connection of two Style D zones to the
Model XR200. See the 869 Installation Guide (LT-0186) and section 25.4 of this guide for wiring information.
16.12 Video Option
The Video option must be selected as NO when any re protection is connected to the XR200. See section
7.9 in the XR200 Programming Guide (LT-0196).
16.13 UL Listed Receivers
UL has veried operation with the DMP SCS-1 or SCS-1R (DD, HST), Sur-Gard SG-HLR2-DG (CID, M2E), FBII
CP220PB (CID), Osborne-Hoffman Quick-Alert (CID, M2E), and Radionics D6500 (M2E) receivers.