18.15 Zone Type Speciî‚¿cations
Zone Information Type
Partition Number
Area Fire
Bell
Wireless
Disarmed
Open
Disarmed
Short
Armed
Open
Armed
Short
Swinger
Prewarn
Entry Delay
Retard Delay
Presignal
Fast Response
Cross Zone
Priority
Style
Assign Area and Disarmed
condition of NT, DY, EX, A1,
A2, and AR only
Assign Prewarn and Entry
Delay for EX only
Assign Retard and Presignal
for FI, SV, A1, A2, and FV
only
Zone Type Defaults
--
DY
FI
EM
A1
FV
NT
EX
PN
SV
A2
AR
INT
BDRM
PERIM
1 to 8
Out
1 to 10
100 to
299
D1 to
D16
G1 to
G20
Message
Output
Action
Message
Output
Action
Message
Output
Action
Message
Output
Action
1
to
4
Y
or
N
A
T
L
-
D
1
to
4
S
P
M
F
A
T
L
-
D
1
to
4
S
P
M
F
A
T
L
-
D
S
1
to
4
S
P
M
F
A
T
L
-
D
S
1
to
4
S
P
M
F
N
or
Y
1
to
8
1
or
4
N
or
Y
1
to
3
N
or
Y
N
or
Y
N
or
Y
TGL
ARM
DIS
STEP
MNT
Night NT - 0 - - 0 - A 0 - A 0 - Y N N N
Day DY T 0 - T 0 - A 0 - A 0 - Y N N N
Exit EX - 0 - - 0 - A 0 - A 0 - Y 1-8 1 N N N
Fire FI 0 T 0 - A 0 - N N + N N N
Panic PN T 0 - A 0 - N N N N
Emergency EM T 0 - A 0 - N N N N
Supervisory SV 0 T 0 - A 0 - N N + N N N
Auxiliary 1 A1 T 0 - A 0 - T 0 - A 0 - N N + N N N
Auxiliary 2 A2 T 0 - A 0 - T 0 - A 0 - N N + N N N
Fire Verify FV 0 T 0 - A 0 - N N N
Arming AR TGL
- = This function is not enabled for this zone type.
+ = Retard must be YES before presignal can be selected.
= These functions are not available for this zone type.
Zone Type Defaults
These are complete spellings of the abbreviations used for the zone types, such as Night and Exit.
Type - These are the abbreviations used for the zone types, such as NT and EX.
Area - For a ALL/PERIM or HOME/SLEEP/AWAY system, this is either Interior, Bedroom, or Perimeter. For an
AREA system, 1 to 8.
Wireless - This zone is connected to a wireless transmitter. For use with the FA400-DMP Remote Wireless
Receiver.
Message - A = alarm report, T = trouble report, L = local, no report, - (dash) = no report,
S = sensor reset/alarm silence (When SV zone is connected to 303 Silence/Reset Switch.)
Output - These are the ten on-board and 200 off-board relay outputs.
Action - This selects the action of the output: S = steady, P = pulse, M = momentary, and F = follow
Swinger - The zone can be automatically shunted after a programmed number of trips.
Prewarn - This selects the keypad address that sounds the entry prewarn for this zone.
Entry Delay - This is the entry delay timer selected as the default for this zone.
Retard Delay - Provides a programmed retard time before an alarm is initiated from a shorted zone. When
used on an arming zone, the retard delay occurs when the zone is shorted before the armed state has
changed. If the arming zone has Maintain as the style, the retard delay also occurs when the zone returns
to a normal state.
Presignal - Provides a keypad tone for zones in retard delay. Retard must be YES before Presignal can be
selected.
Fast Response - Provides a 167ms zone response instead of the normal 500ms response.
Cross Zone - Provides cross zoning with any of the 242 available zones.
Priority - Requires this zone to be in a normal condition before the area can be armed.
Style - The abbreviations for arming zone style: TGL = Toggle, ARM = Arm only, DIS = Disarm only,
STEP = Wireless arming, MNT = Maintain