Programming instructions
Digital Monitoring Products XR200-485 Programming Guide
44
APPENDIX
XR200-485 Programming Guide Digital Monitoring Products
45
APPENDIX
Then, from the panel, enter 984 and the COMMAND key, while the panel displays in the Status List. The
keypad display changes to NBR RMT PICKUP. Press the Select key under RMT. The panel automatically
calls the receiver connected to Remote Link to download the new programming. Remote Link then traps
the panel.
Note: The panel makes ten attempts to reach the receiver. If while attempting to contact the receiver, the
panel needs to send an alarm report, the panel stops dialing and uses the phone line to send its report.
PICKUP
After completing panel programming in Remote Link, connect to the panel by selecting Panel > Connect.
Refer to the Remote Link User’s Guide, LT-0565, or Remote Link Help File for complete information about
connecting to panels.
When the telephone line at the panel rings, enter 984 and the COMMAND key, while the panel displays
the Status List. The keypad display changes to NBR PICKUP. Press the Select key under PICKUP to
allow the panel to seize the line. The panel immediately seizes the phone line and sends a carrier tone
to the receiver. A verication process occurs and, if successful, the panel grants remote access to its
programming and Event Buffer.
After the panel has seized the line, send the le from Remote Link by selecting Panel > Send. Remote
Link then uploads the new programming into the panel. You may also Request Events by selecting Panel >
Request Events in Remote Link.
Keypad Displays
When using either the RMT or PICKUP options, the keypad displays LINE SEIZED. This indicates that the
panel has seized the line and is executing its program. If the line cannot be accessed, or if the RMT or
PICKUP options are used before all connects attempts are made, the keypad displays SYSTEM BUSY.
18.3 Using the Walk Test
The XR200-485/485B panel provides a walk test feature that allows a single technician to test the
protection devices connected to zones on the system. To conduct the Walk Test, reset the panel.
WALK TEST
Walk Test
To conduct the Walk Test, reset control panel by momentarily placing a jumper
on J16. From the keypad, enter the code 8144 and press COMMAND. The
keypad displays WALK TEST for four seconds. If the system is monitored and the
communication type is DD or HST, the system sends a System Test Begin report to the
central station. After four seconds, the keypad displays the zone type choices for
testing.
*BG *FI *PN *SV
Zone Types
Press the Select key directly below the zone type you want to test. An asterisk
next to the zone type indicates the zone type chosen for testing. Press the select
key again to deselect the zone type. When you have selected all the zone types
you want for testing, press the COMMAND key to display the next Walk Test option.
Pressing the Back Arrow key exits the Walk Test.
BG (Burglary zones) - Select BG to test burglary zones. Includes all NT, DY, EX, A1,
and A2 zones.
FI (Fire zones) - Select FI to test re zones. Includes all FI and FV zones.
PN (Panic zones) - Select PN to test panic zones. Includes all PN and EM zones.
Note: While testing the panic zones in the Walk Test, trip each panic zone (or
button) on the system by pressing and holding the panic for 1 to 2 seconds.
You do NOT have to hold the panic for 2 seconds in normal mode. You are only
required to hold the panic during the Walk Test because the zone takes additional
time to report when the system is in test mode.
SV (Supervisory zones) - Select SV to test supervisory zones. Includes all SV zones.
Note: During the Walk Test, trip each panic zone (or button) on the system by
pressing and holding the panic for 1 to 2 seconds.