Programming instructions

Digital Monitoring Products XR200-485 Programming Guide
22
OUTPUT OPTIONS
XR200-485 Programming Guide Digital Monitoring Products
23
OUTPUT OPTIONS
8.5.12
DVC FAIL OUT: 0
Device Fail Output
Enter the output number to turn on when an addressed device fails to respond to
polling from the panel. A Missing Device report is sent to the receiver. The output
is turned off when the device responds to polling or is removed from the system.
Enter zero to disable this output and LX-Bus™ device fail reporting to the receiver. If
any addressed device is unsupervised, this output cannot be used.
8.5.13
SNSR RST OUT: 0
Sensor Reset Output
Enter the output number to turn on when a Sensor Reset is performed at a keypad.
The output turns off automatically 5 seconds later. This function can be used to
reset smoke detectors operated by an external power supply through a Model 716
Output Expander Module. Enter zero to disable this output.
8.6
OUTPUT NAMES . . .
Output Names
This section allows you to dene a 16 character alphanumeric name for any or all
210 output numbers. The name can display on the keypad when a user performs the
browser feature at Outputs On/Off. See the XR200-485/485B User’s Guide (LT-0364)
Appendix for browser operation.
8.6.1
OUTPUT NO: -
Output Number
Enter an output number (1 to 10, 100 to 299).
8.6.2
OUTPUT NAME X X X
Output Names
The output name displays. To change the default name, press any top row Select
key then enter up to 16 characters for the output name. Press COMMAND to enter
the next output number and name.