Programming instructions

Digital Monitoring Products XR200-485 Programming Guide
8
COMMUNICATION
XR200-485 Programming Guide Digital Monitoring Products
9
COMMUNICATION
3.3
2ND LINE: NONE
2ND Phone Line
Allows you to use a second communication line to send reports to the SCS-1/SCS-1R
Receiver should the rst phone line fail. The default 2nd Phone Line is NONE.
If 2ND LINE is DD or CELL (and you are not using a 462N Network Interface Card), you
need to install a DMP 893 or 893A Dual Phone Line Module to connect both the main
and secondary phone lines to the panel.
Both DD and MPX type systems can be backed up with a dialer or cellular line.
Multiplex lines cannot be used as a secondary line.
NONE DD CELL HST
NONE - A second line is not used.
DD - Dialer communication to a DMP SCS-1/SCS-1R Receiver. When using M2E or
CID as the main Communication Type, choose DD to communicate to an M2E or CID
receiver on the 2ND LINE.
CELL - Cellular dialer communication with Cell-Miser™ restrictions. When Cell-Miser
is selected, the following call restrictions apply to the panel.
1. Only zone alarms, Ambush, Line 1 Trouble, Abort, Recall Test, and Delayed
Events are sent over the cellular system. Delayed Events are only sent if the
cellular call was made for one of the other allowed reports.
2. Line 1 Trouble is sent only once during each armed period.
3. The dialing sequence uses the rst phone number on line 1 only and the second
phone number on line 2 only. This allows the panel to use the cellular phone
number for cellular calls only without needing prexes or area codes for land
line dialing.
If 2ND LINE = DD If 2ND LINE = CELL
Panel dials the 1st ph # twice on Line 1 Panel dials the 1st ph # twice on Line 1
Panel dials the 1st ph # twice on Line 2 Panel dials the 2nd ph # twice on Line 2
Panel dials the 2nd ph # twice on Line 1 Panel dials the 1st ph # twice on Line 1
Panel dials the 2nd ph # twice on Line 2 Panel dials the 2nd ph # twice on Line 2
Panel dials the 1st ph # twice on Line 1 Panel dials the 1st ph # twice on Line 1
NONE DD CELL D2
D2 - Select D2 to allow supervision of a second telephone line connected to a
Model 893 or 893A Dual Phone Line Module. D2 is only displayed if HST is the main
Communication type.
NONE DD CELL HST
HST (HOST) - DMP Asynchronous communication to a DMP SCS-1/SCS-1R Receiver or
Host automation system. If HST is selected as the Communication Type, HST does
not display as an option in 2ND LINE. If HST is selected for 2ND LINE, all zone alarms
and restorals are duplicated on the asynchronous channel in addition to the main
communication method.
When HST is used as the main or 2ND LINE communication method, the account
number must not begin with a number that matches a line number being used
for multiplex service on the same SCS-1 Receiver. This allows the Redisplay Non-
Restored status list to work properly in receivers with SCS-1/805 or higher rmware.