PROGRAMMING GUIDE XR200-485 ACCESS CONTROL COMMAND PROCESSOR™ PANEL
MODEL XR200-485/485B ACCESS CONTROL COMMAND PROCESSOR™ PANEL PROGRAMMING GUIDE Contains programming instructions for use with the Model 485 and 485B Access Control Expansion card. When using the XR200-485/485B panel for any UL, NFPA, CSFM, or other listing organization’s approved methods, refer to this manual and the XR200 Installation Guide (LT-0197). These documents outline the installation and programming requirements of all applications for which the XR200-485/485B is approved.
TABLE OF CONTENTS Revisions to This Document.............................................vi Introduction......................................................................1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 Before you Begin.................................................................... 1 Internal Programmer.............................................................. 1 Programming Information Sheet ............................................. 1 Getting Started .................................
TABLE OF CONTENTS 3.21 3.22 3.23 3.24 3.25 3.26 3.27 3.28 3.29 3.30 Pager Type ...........................................................................13 Alarm Reports .......................................................................13 Supervisory/Trouble Reports ..................................................13 Opening/Closing and User Reports..........................................13 Test Report ...........................................................................
TABLE OF CONTENTS Output Options ...............................................................21 8.1 8.2 8.3 8.4 8.4.1 8.4.2 8.4.3 8.4.4 8.4.5 8.4.6 8.4.7 8.5 8.5.1 8.5.2 8.5.3 8.5.4 8.5.5 8.5.6 8.5.7 8.5.8 8.5.9 8.5.10 8.5.11 8.5.12 8.5.13 8.6 8.6.1 8.6.2 Output Options .....................................................................21 Bell Cutoff Time ....................................................................21 Automatic Bell Test .........................................................
TABLE OF CONTENTS Printer Reports ...............................................................28 12.1 12.2 12.3 12.4 12.5 12.6 Printer Reports......................................................................28 Arm and Disarm Reports ........................................................28 Zone Reports ........................................................................28 User Command Reports .........................................................28 Door Access Reports.......................
TABLE OF CONTENTS 15.16 15.17 15.18 15.19 15.20 15.21 15.22 15.23 15.24 15.25 15.26 15.27 15.28 Output Action........................................................................38 Swinger Bypass .....................................................................39 Prewarn Addresses ................................................................39 Entry Delay ...........................................................................39 Zone Retard .....................................................
REVISIONS Revisions to This Document This section explains the changes made to this document during this revision. It lists the date and identifies the change made, the related section number and section heading, and a summary of the change. Date Section Number and Heading Quick Explanation of Changes 8/05 14.10 Early Morning Ambush 15.20 Zone Retard Clarified second user code operation. Expanded and clarified operation. 3/04 Entire Document Added iCOM-E where applicable corrected 4.
INTRODUCTION Introduction 1.1 Before you Begin This guide provides programming information for the DMP XR200-485/485B Command Processor™ Panel. After this Introduction, the remaining sections describe the functions of each programming menu item along with the available options. Before starting to program, we recommend that you read through the contents of this guide. The information contained here allows you to quickly learn the programming options and operational capabilities of the XR200-485/485B panel.
INTRODUCTION Accessing the Programmer 1. Install the reset jumper across the two J16 reset pins for two seconds. See Figure 1. 2. Remove the reset jumper and place it over just one pin for future use. 3. Enter the code 6653 (PROG) into an alphanumeric keypad set to address one. Press COMMAND. 4. The keypad displays PROGRAMMER. You are now ready to start programming the panel.
INTRODUCTION 1.5 Reset Timeout The panel has a feature that requires you to enter the Programmer within 30 minutes of resetting the panel. After 30 minutes, if you attempt to program by entering the 6653 (PROG) code, the keypad displays: RESET PANEL. You must reset the panel, enter the program code, then begin programming within the next 30 minutes. If you are already in the Programmer and do not press any keys on the programming keypad for 30 minutes, the panel terminates programming.
INTRODUCTION 1.8 Entering Non-Alpha Characters To enter a space in an alpha entry, press the 9 digit key followed by the third Select key. The three characters on the 9 digit key are Y, Z, and space. You can also enter the following characters: – (dash), . (period), * (asterisk), and # (pound sign) using the zero key and the four Select keys from left to right. For example, to enter a – (dash), press the zero key and then the left Select key. A dash now appears in the keypad display.
INITIALIZATION Initialization 2.1 INITIALIZATION Initialization This function allows you to clear and return selected parts of the panel program back to the factory defaults in preparation for system programming. ������������������������������������������ ����������������������������������������������� ������ �� ��� ������������������������������ ���������������������� ����� ���������������������� ����������������������� ������� 2.
COMMUNICATION Communication 3.1 COMMUNICATION Communication Configure the communication options for the panel. The information you program varies with the Communication Type you select. 3.2 COMM TYPE: DD Communication Type Specifies the communication method the panel uses to report system events to DMP SCS-1/SCS-1R Receivers or non-DMP receivers. Press any Select key. NONE - For local systems. Selecting NONE ends communication programming.
COMMUNICATION 3.2.2 HST BCKUP NO YES Host Backup After displaying the Retry time prompt, the keypad displays HST BCKUP NO YES. Select YES to enable Host Backup. Select NO to disable Host Backup. You can still program 2nd line for a different communication type, such as CELL or DD. Note: Refer to the Appendix for more information about using Host Backup. 3.2.3 TEST FREQ: NONE NONE REG 7 30 Test Frequency Specifies the communication test interval for the host backup.
COMMUNICATION 3.2.5 UL AA NO YES UL AA At the UL AA prompt, select Yes to enable AA Mode or NO to disable AA Mode. NO is the default setting. UL AA involves check-in reports. Check-in reports are a method of supervising the panel communication with the receiver. To be UL AA compliant, panels must check-in with the receiver every 6 minutes when armed. The SCS-1/SCS-1R Receiver verifies that the next Check-in report is received at the appropriate time.
COMMUNICATION 3.3 2ND LINE: NONE 2ND Phone Line Allows you to use a second communication line to send reports to the SCS-1/SCS-1R Receiver should the first phone line fail. The default 2nd Phone Line is NONE. If 2ND LINE is DD or CELL (and you are not using a 462N Network Interface Card), you need to install a DMP 893 or 893A Dual Phone Line Module to connect both the main and secondary phone lines to the panel. Both DD and MPX type systems can be backed up with a dialer or cellular line.
COMMUNICATION 3.3.1 TEST FREQ: NONE Test Frequency NONE REG 7 NONE - No communication test is made on the second line. NONE is selected by default. 30 Specifies the communication test interval for the second phone line. This is displayed if 2ND LINE is programmed as DD, CELL or HST. REG - A 2ND LINE communication test is made each time the regular communication test is completed. 7 - A communication test is made every 7 days at the test time programmed for the regular communication test.
COMMUNICATION 3.8 3.9 DFR TEST NO YES TEST FREQ: 0 Defer Test Time Select YES to allow the programmed test report to be deferred if the panel communicates with a receiver within the time set in Test Frequency. Select NO to send the test report as programmed regardless of previous panel communication. Test Frequency Allows you to set how often the panel sends a test report to the SCS-1/SCS-1R Receiver. Enter from 1 to 60 days. This prompt is not displayed if Defer Test Time is NO. 3.
COMMUNICATION 3.11 3.12 RECEIVER 1 PROG ALARM NO YES Receiver 1 Programming Allows you to set the options for the first receiver the panel attempts to contact when sending reports. The panel supports communication to two receivers. Alarm Reports YES sends Abort, Alarm, Alarm Restoral, Ambush, Exit Error, and System Recently Armed reports to this receiver. 3.
COMMUNICATION 3.20 3.21 RECEIVER 2 PROG PAGER? NONE Receiver 2 Programming Allows you to set the options for the second receiver the panel attempts to contact when sending reports. If you select YES for any of the second receiver options, you must have at least one phone number programmed in Receiver 2 programming. RECEIVER 2 PROG and the following prompts do not display if COMM TYPE is HST and 2ND LINE is NONE.
DEVICE SETUP Device Setup 4.1 Device Setup DEVICE SETUP This section allows you to define the XR200-485/485B panel physical configuration. You can install and address up to sixteen supervised devices on the keypad data bus. Zones are available only from addresses 1-8. Additionally, certain device functions are programmed in address pairs; 1-9, 2-10, 3-11, 4-12, 5-13, 6-14, 7-15, and 8-16. These options include Partition (4.4), Access Keypad Reports (6.7), Menu Display (9.1), Status List (10.
DEVICE SETUP 4.7 ACCESS - - - - - - - - Access Areas Enter the area numbers (1 to 8 for partition 1 and 1 to 4 for partitions 2, 3, and 4). Users must have matching access area numbers assigned to their code to receive door access at this device. If you do not enter any area numbers, all users with Door Access authority will receive door access without regard to schedules. If the user code is programmed for Anti-Pass YES, then the user is logged into all matching areas.
REMOTE OPTIONS Remote Options 5.1 Remote Options REMOTE OPTIONS This section allows you to enter the information needed for Remote Command/ Remote Programming operation. 5.2 Remote Key RMT KEY: This option allows you to enter a code of up to eight digits for use in verifying the authority of an alarm or service receiver to perform a remote command/ programming session. The Remote Link™ program must give the correct key to the panel before being allowed any remote functions.
REMOTE OPTIONS 5.7 SVC REC NO YES Service Receiver Authorization YES enables remote commands and programming to be accepted from a secondary service receiver other than the alarm SCS-1/SCS-1R Receiver. The Remote Key option can also be required. With YES selected, the panel requests the service receiver key the first time it is contacted by the service receiver. The panel retains this service receiver key in memory and accepts remote commands from the service receiver.
SYSTEM REPORTS System Reports 6.1 SYSTEM REPORTS System Reports Select specific system reports the panel sends to the receiver. 6.2 ABORT NO YES Abort Report YES allows the panel to send an alarm abort report to the receiver any time an area is disarmed after an alarm report has been sent and the Bell Cutoff Time has not expired. No alarmed zones can still be armed. Abort reports are also sent when the system is disarmed during Transmit Delay and the Bell Output Timer is active.
SYSTEM OPTIONS System Options 7.1 System Options SYSTEM OPTIONS This section allows you to select system-wide parameters. 7.2 CLS WAIT NO YES Closing Wait When YES, the keypad displays ONE MOMENT... while the system waits for an acknowledge from the receiver before arming the selected area(s) and performing a Bell Test (if selected). Exit delays begin after the Closing Wait. Opening/Closing reports must be YES to enable Closing Wait. 7.3 7.
SYSTEM OPTIONS 7.8 7.9 RST SBYP NO YES Reset Swinger Bypass VIDEO NO YES Video/Alarm Verification When YES is selected, an automatically bypassed zone is reset if it remains in a normal condition for one complete hour after being bypassed. An automatic reset report is sent to the receiver if Bypass Reports is selected as YES. Selecting YES forces the panel to wait for 60 seconds after a successful communication with a central station receiver before making any additional communication attempts.
OUTPUT OPTIONS Output Options 8.1 Output Options OUTPUT OPTIONS This function allows you to program the panel Bell Output functions and certain Relay Output options. Dry contact relays and voltage outputs are available using the XR200-485/485B board output harness. Refer to the XR200 Installation Guide (LT0197) for complete information. 8.2 BELL CUTOFF: 15 Bell Cutoff Time Enter the maximum time from 1 to 99 minutes the Bell Output remains on.
OUTPUT OPTIONS 8.5.2 CUTOFF TIME: 0 Output Cutoff Time If a Cutoff Output is assigned, enter a Cutoff Time of 1 to 99 minutes for the output to remain on. Enter zero for continuous output. 8.5.
OUTPUT OPTIONS 8.5.12 DVC FAIL OUT: 0 Device Fail Output Enter the output number to turn on when an addressed device fails to respond to polling from the panel. A Missing Device report is sent to the receiver. The output is turned off when the device responds to polling or is removed from the system. Enter zero to disable this output and LX-Bus™ device fail reporting to the receiver. If any addressed device is unsupervised, this output cannot be used. 8.5.
OUTPUT GROUPS Output Groups 9.1 OUTPUT GROUPS Output Groups This function allows you to assign outputs to groups. Output groups can be assigned to other areas of programming such as Output Options or Zone Information Alarm Action, the same way single outputs are assigned. This allows the entire group of outputs to turn on and off as required by the programming option. 9.2 GROUP NO: - Group Number Enter a group number from 1 to 20. Up to 20 different groups may be assigned. 9.
MENU DISPLAY Menu Display 10.1 MENU DISPLAY Menu Display Menu Display allows you to select at which keypad addresses the user can access the following functions. Menu displays for addresses 9-16 automatically show when a corresponding address 1-8 is entered. For example, when address 1 is entered for Time Display, address 9 also displays the time. 10.2 ARM STAT 12345678 Armed Status Enter the keypad addresses that show the armed areas for their partitions.
STATUS LIST Status List 11.1 STATUS LIST Status List This function allows you to select the zone alarms and troubles, and system monitor troubles displayed at the keypads. The Status List function operates automatically when the keypad is not performing any other function. Status list displays for addresses 9 through 16 automatically show when a corresponding address 1 through 8 is entered. The keypad stays in the Status List until the user arms or disarms or selects a menu option.
STATUS LIST 11.5 BURGLRY 12345678 Burglary Zones Specifies the addresses where all burglary zone alarms and troubles display. Burglary zones include Night, Day, and Exit type zones. Burglary zone troubles remain in the list until the zone restores. All keypads are selected by default. For zone alarms, only the last burglary zone tripped remains in the list. The alarm remains in the list until another burglary zone goes into alarm, any area of the system is disarmed, or 10 minutes elapses without an alarm.
PRINTER REPORTS Printer Reports 12.1 PRINTER REPORTS Printer Reports This section allows you to define the operation of a local printer connected to the panel through the use of a DMP 462P Printer Interface Card. The 462P allows you to connect the DMP SCS-PTR or other compatible 40-character or 80-character serial printer to the panel.
HOST LOG REPORTS Host Log Reports 13.1 HOST LOG REPORTS Host Log Reports This section allows you to program the types of logging reports the panel will send through the 462N Network Interface Card. The reports include information such as the type of activity, time and date of the activity, and user name and number. These data logging reports can be accessed using the Advanced Reporting Module. See the User’s Guides for more information.
AREA INFORMATION Area Information 14.1 AREA INFORMATION Area Information Allows you to assign functions to the different areas within a partition. All non-24hour zones must be assigned to an active area. See Zone Information. You activate an area by assigning it a name. See Area Name. A name is given to each active area in place of a number to assist the user during arming and disarming. 14.2 PARTITION NO: 1 Partition Number Enter the partition number to program.
AREA INFORMATION 14.7 CLS CODE NO YES Closing Code When YES is selected, a code number is required for system arming. If NO is selected, a code number is not required for system arming. 14.8 ANY BYPS NO YES Any Bypass When YES is selected, zones can be bypassed without a code number during the arming sequence. A code number is always required to use the Bypass Zones option from the menu. 14.
AREA INFORMATION 14.13 ACCOUNT NO: 12345 Account Number Enter the account number to be sent to the receiver for this area. Choose an account number compatible with the Communication Type selected in Communications. The default Account Number is the one previously entered. If the Communication Type selected multiplex, you must choose an account number between 128 and 999.
AREA INFORMATION 14.19 BANK/SAF NO YES Bank Safe & Vault (485B only) NO disables the Bank Safe & Vault feature for this area. When selected as YES, schedules set for this area and the time of day cannot be changed while the area is armed. Program schedules before arming: A Bank Safe & Vault area can only be disarmed during scheduled times.
ZONE INFORMATION Zone Information 15.1 ZONE INFORMATION Zone Information Zone Information allows you to define each protection zone operation used in the system. All protection zones, whether located on a command processor panel, Security Command keypad, or zone expander are programmed the same way. 15.2 ZONE NO: - Zone Number Enter the zone number you intend to program. Available zone numbers are shown in the table below. Press COMMAND to enter a zone name.
ZONE INFORMATION 15.4 ZONE TYPE: BLANK Zone Type The Zone Type defines the panel response to the zone being opened or shorted. This is called the Alarm Action. There are up to 13 possible alarm action responses depending on the zone type and any restrictions it may have. See Sections 18.4 and 18.5 in the Appendix for Zone Type information. When you assign a Zone Type to a zone, responses are made automatically for the zone. There are 12 Zone Types to choose from.
ZONE INFORMATION 15.8 AREAS: 1234 Arming Zone Area Assignment If the zone has been programmed as an Arming Type (AR), the only information to enter is the areas that the zone controls. When the zone changes from normal to shorted, the programmed areas toggle between the armed or disarmed condition. When restored to normal, no action occurs. When the zone opens from a normal (disarmed) state, a trouble is reported.
ZONE INFORMATION 15.10 NEXT ZN? NO YES Next Zone When YES is selected, the programming for the zone terminates and the display returns to Zone Number, allowing you to enter a new zone number. To make any alterations to the Alarm Action for a zone, answer the Next Zone prompt with NO. The Alarm Action is then defined in the following sections. NOTE: Sections 15.10.1 through 15.10.5 are only used with FA400 Remote Wireless Receivers and 472 interface card.
ZONE INFORMATION 15.14 MSG: A TROUBLE T L - Report to Transmit Press any Select key to display the following report options: A, T, L, S, and - (dash). ALARM - Select A to send an alarm report to the receiver and activate the bell output according to zone type. The zone name appears in the panel’s alarmed zones and status lists. TROUBLE - Select T to send a trouble report to the receiver. The zone name appears in the panel’s alarmed zones and status lists.
ZONE INFORMATION 15.17 SWGR BYP NO YES Swinger Bypass YES allows the zone to be swinger bypassed by the panel according to the specifications programmed in Swinger Bypass Trips and Reset Swinger Bypass. The Bypass condition displays in the keypad Status List. Selecting NO disables swinger bypassing for this zone.
ZONE INFORMATION 15.23 CRS ZONE NO YES Cross Zone Select YES to enable cross zoning for this zone. Cross zoning requires one or more armed zones to fault within a programmed time before an alarm report is sent to the receiver. When a cross zoned zone trips, the bell action assigned to the zone activates. The cross zone time specified in System Options begins to count down.
STOP Stop 16.1 STOP Stop At the STOP prompt, pressing any Select key allows you to exit the panel Programmer function. When selected, the panel performs an internal reset and exits the programmer. The STOP routine causes the following conditions to occur: • All areas in all partitions are DISARMED • All zones in all partitions are DISARMED • The panel Status List is CLEARED During the reset, all keypad displays are momentarily blank for two seconds.
APPENDIX Appendix 18.1 Diagnostics Function The XR200-485/485B panel contains a Diagnostics function that allows LX-Bus™ communication integrity testing, identifies individual zones, and displays the present state of any zone. To use Diagnostics, reset the panel, enter the Diagnostics code 2313 (DIAG), and press COMMAND. Test LX-Bus The first Diagnostic function you see displayed is: TEST LX-BUS.
APPENDIX Overlap An overlap occurs when a device address is the same as any of the last three zones on another 714 or 715. Note: The overlap feature cannot determine when two devices have the same address. Example 714 Address 00 711 Address 02 Zones 100 101 102 103 Zone 102 Overlap Missing Missing occurs when a zone between 100 and 299 has been programmed in ZONE INFORMATION and no device with that zone address is installed on the LX-Bus.
APPENDIX Then, from the panel, enter 984 and the COMMAND key, while the panel displays in the Status List. The keypad display changes to NBR RMT PICKUP. Press the Select key under RMT. The panel automatically calls the receiver connected to Remote Link to download the new programming. Remote Link then traps the panel. Note: The panel makes ten attempts to reach the receiver.
APPENDIX BELL NO YES Bell Action This option selects the bell output action when a zone under test faults. This option allows the panel bell, and/or burglary bell, and/or fire bell to turn ON and then OFF each time a zone trips (opened or shorted). NO - Select NO for no bell output action during Walk Test. YES - Select YES to turn on any bell output for 2 seconds during Walk Test. PULS - Select PULS to turn on any bell output for 1/4 second during Walk Test. Any LX-Bus device output turns on for 1.
APPENDIX 18.6 Pager Direct Specifications The XR200-485 communicates in full-duplex mode with a Glenayre alphanumeric pager terminal. The terminal modem must accept the following parameters: • 300 bps Bell 103 protocol • Carrier detect response time = 300ms • Delay between lost carrier and hang-up = 12.
APPENDIX 18.9 Host Backup Examples Several examples follow to explain scenarios in which you would use Host Backup and how to program the panel for Host Backup. When using Host Backup with Host Log Reports, refer to the next section, 462N Network Interface Card Examples. Example 1: Two 462N Cards This example describes the configuration and programming needed when you are using two 462N Cards and two iCOMSL units to enable the Host Backup.
APPENDIX 18.10 462N Network Interface Card Examples Several options are available when configuring the panel for Host communication, Host backup communication, and Host Log Reports. All options use a 462N card and an iCOM Internet Alarm Router or iCOM-E Encrypted Internet Alarm Router (an iCOM or iCOM-E is not required for the Host Log Reports when using a direct connection). The chart below outlines the different ways you can configure the panel for these three options.
APPENDIX 18.
APPENDIX 18.14 Zone Type Descriptions This section describes applications for the default zone types in Zone Information programming. -- (Blank Zone) Customizable zone type. By default, no actions are programmed to occur with Blank Zone. A zone name must be entered to use this zone type: This zone type is not the same as an *UNUSED* zone. NT (Night Zone) Controlled instant zone used for perimeter doors and windows and interior devices such as PIRs and Glassbreak detectors.
APPENDIX N 1 S to P 4 M F A T L D S 1 S to P 4 M F A T L D S 1 S N to P 4 M or F Y 1 1 N 1 N N N to or or to or or 8 4 Y 3 Y Y TGL ARM or DIS Y STEP MNT Night NT - 0 - - 0 - A 0 - A 0 - Y N N N Day DY T 0 - T 0 - A 0 - A 0 - Y N N N Exit EX - 0 - - 0 - A 0 - A 0 - Y N N N Fire FI T 0 - A 0 - N N N N 0 1-8 1 N + Panic PN T 0 - A 0 - N N N N Emergency EM T 0 - A 0 - N N N N Supervisory SV T
APPENDIX 18.16 Common Keypad Messages There are several common keypad messages that the keypad displays to inform the technician and end-user. The common messages are described below. Possible solutions are also provided. Message Meaning Possible Solutions INVALID AREA The user has attempted a door access for an area they are not assigned. Change the user access areas if access to the area is needed. If access is not needed, the user cannot enter the area.
APPENDIX This page intentionally left blank XR200-485 Programming Guide Digital Monitoring Products 53
Underwriters Laboratories (UL) Listed UL 294 Access Control System Units UL 365 Police Connected Burglar UL 609 Local Burglar UL 864 Fire Protective Signaling UL 985 Household Fire Warning UL 1023 Household Burglar UL 1076 Proprietary Burglar UL 1610 Central Station Burglar UL 1635 Digital Burglar UL Bank Safe and Vault (485B only) California State Fire Marshal (CSFM) FCC Part 15 FCC Part 68 Registration ID CCKUSA-18660-AL-R 800-641-4282 INTRUSION • FIRE • ACCESS • NETWORKS www.dmp.