BUEP03E Protocol8-34
The fault information is written to the R5CON checkback parameters in
the following sequence:
P3 parameter
HIGH byte LOW byte
Status PLC response
P4 parameter
HIGH byte LOW byte
Error class Error code
8.8.1 Job Status
The current status of the job is specified in the Status by the function mo-
dule:
Status Explanation
00H Job ended fault-free
01H Job written to queue
02H Job processing
03H Job ended with fault(s)
Fig. 8-16 BÜP03E — Job status
8.8.2 PLC Response
The PLC response is intended to provide the user with advice and help on
the faults within the fault information.
The following conventions apply:
PLC response Explanation
00H No response, job fault-free
01H Repeat FM job
02H Program fault, change PLC program
03H Change protocol parameter
04H Rerun the program cycle on the R5INIT
05H Rerun the program cycle on the R5REQ
06H Rerun the program cycle on the R5CON
07H Reload the protocol
09H Repeat the job
10H Active job terminated by the user
20H Job fault-free, however with reduced data length
Fig. 8-17 BÜP03E — PLC Response