Specifications

1070 072 131-102 (96.08) GB
BUEP19E Protocol 7-13
Fault information
PLC
response
Error class Error code Explanation
03 32 02 Memory access fault (PST)
Faults occurred when RST memory area was accessed: Data
incorrectly read or incomplete.
03 32 03 Wrong memory type (PST)
The type of access for the addressed PST memory is not per-
mitted (e.g. writing to EPROM)
03 32 05 Internal communications fault (PST)
Fault during the processing of a command
03 32 20 Command code unknown (PST)
03 32 21 Protocol identifier unknown (PST)
03 32 23 Invalid coordination marker (PST)
03 32 25 Wrong parameterisation (PST)
03 32 26 Block-length fault (PST)
03 32 28 Message type unknown (PST)
03 32 29 Command type unknown (PST)
03 32 3A Wrong address alignment (PST)
03 32 3B Invalid address area (PST)
03 32 3C Invalid parameter (PST)
03 32 3D Invalid operand type (PST)
03 32 40 Identification still not implemented (PST)
03 32 63 Buffer overflow. The data length is larger than the available
memory location of 800H bytes.
03 32 D2 Coordination marker disabled
Occurs only for field coordination
03 30 01 No module (RST)
03 30 10 Module not addressable (RST)
The indicated block address has no module number
03 30 21 RUN fault (RST)
03 30 22 Operating mode cannot be changed (RST)
03 30 23 Field access prohibited (RST)
03 30 24 Field protection active (RST)
03 30 25 Timer disabled (RST)
03 30 26 Module number too large (RST)
03 30 27 No data module (RST)
03 30 28 Data module too small (RST)
03 30 29 Monitor disabled (RST)
03 30 2B System-clock fault (RST)
03 30 2C Reference-list entry cannot be changed (RST)
03 33 10 No valid block addr. for the indicated module number
03 33 20 Wrong RST command code
03 33 23 Command for RST larger than 80H
03 33 29 Wrong command type
03 33 3C No module type for indicated module number
03 33 3D Wrong operand type
03 33 47 Wrong data length
10 31 60 Passive job terminated
10 31 61 Active job terminated
20 ‘Length’ Job fault-free, requested data length <> recommended data
length
Fig. 7-16 BÜP19E — Fault messages, Part 2