Specifications
1070 072 131-102 (96.08) GB
BUEP19E Protocol7-2
7.2 Protocol-specific Settings
The S2 DIP switch for the BÜP19E protocol has the following function:
Switch Setting Explanation Channel
SS1 ON
OFF
peripheral jobs have priority
centralised jobs have priority
0
SS2 - no function 0
SS3 - no function 0
SS4 - no function 0
SS5 ON
OFF
peripheral jobs have priority
centralised jobs have priority
1
SS6 - no function 1
SS7 - no function 1
SS8 - no function 1
Fig. 7-1 BÜP19E — S2 DIP Switch settings
NOTE –
When installing the link, ensure that the low priority is assigned to
one unit and the high priority is assigned to the other unit.
7.3 Protocol-specific Parameters
The BÜP19E uses protocol-specific parameters to parameterise the data
traffic for RST and PST. Each parameter is explained below.
7.3.1 Command Type / Operand Type Parameters
Parameter word Contents
HIGH byte LOW byte
PW4 Type of command Type of operand
Example 41H 01H
Output Word
Fig. 7-2 BÜP19E — Command type / Operand type