Specifications

1070 072 131-102 (96.08) GB
R5CON Confirmation Module 6-1
6 R5CON Confirmation Module
6.1 Characteristic Data
Characteristic data R5CON
Module name R5CON
Block length 473 words
Call-up length 6 words
Number of parameters 5
Used markers M230 to M254
Fig. 6-1 R5CON — Characteristic data
The R5CON Confirmation module monitors the centralised jobs. Its
function is to return information to the user while the job is processing and
after the job has ended. The module retrieves the status and the fault
word from the job table and transfers this information to the address
which the user indicated as a parameter.
The R5CON confirmation module can be used to acknowledge either only
one job per call-up or all fault-free jobs and one defective job. The
R5CON retrieves the status and the fault word from the job table and
transfers them to the PLC program. However, if all fault-free jobs are
acknowledged, the status and the fault word contain only the information
which relates to the one permitted defective job.
The R5CON should acknowledge all jobs issued by the R5REQ; the re-
sults of the individual jobs are read out. A local acknowledgement is ge-
nerated for unconfirmed services.
A new job cannot be started with this number until the acknowledgement
has been read out.