Specifications
1070 072 131-102 (96.08) GB
Hardware Description2-12
2.8 Protocol Loader
The transfer protocols are loaded onto the R500 or R500P by means of
the PROFI software.
The protocol loader for the R500 or R500P module is located in the loader
under the Configuration menu option.
The protocols are loaded into the R500 module by the SK500 or the
ZS400.
The protocols must be filed in the BOSCH.BIB subdirectory.
2.9 R500 Specifications
Specifications R500
Interfaces V.24/20 mA according to VDE 2880
Page 2
both interfaces are isolated
Baud rates 110 to 19200 bps
V.24/20 mA interface
Power consumption from 5 V voltage
supply
430 mA typically
690 mA maximum
Power consumption from 5 V (Vp) typically 7 mA (operation)
Power consumption from 3.5 V (Vp) typically 2 mA (standby)
Power consumption from +12V- ISO
voltage supply
140 mA
+ 20 mA per active current loop
Power consumption from -12V- ISO
voltage supply
20 mA typically
Resistance to line transient interference
of mains supply
as per DIN EN 61131-2
Max. number of modules per controller 5
Ambient temperature range 0 to +55 °C
Storage temperature range -25 to +70 °C
Modular width single
Weight 590 g
Fig. 2-11 R500 — Specifications