Specifications

1070 072 131-102 (96.08) GB
BUEP64 Protocol9-32
9.12.2 FETCH Job (CL500 <- CL300)
Thirty-three (33) words, beginning with the byte address 1AH (word num-
ber DH, see Chap. 9.2), are read from the DM12 data module in the
ZE301 and written, without coordination, to the DM27 data module in the
ZS3 with block address 18H from byte address 50H (word number 28H,
see Chap. 9.2).
The transfer is processed by Channel 0 of the R500 with the number 3
(CXN3 see R5INIT parameterisation).
The job receives job number 7.
The job is parameterised as follows:
Param. word Contents Explanation
PW1 --- No entry
PW2 0300H CXN3, Channel 0
PW3 7H Job number 7
PW4 4501H Output job (FETCH) / word
PW5 4444H RST code: DM PST code:
DM
PW6 1BH RST address: DM number 27
PW7 18H RST address: Block addr. ZS3 = 18H
PW8 28H RST address: Data word no. 40
PW9 CH PST address: DM no. 12
PW10 --- No entry
PW11 DH PST address: Data word no. 13
PW12 21H Volume of data: 33 words
PW13 FFFFH Without coordination
PW14 --- No entry
PW15 --- No entry
PW16 --- No entry
Fig. 9-17 BÜP64 — Example of FETCH parameters (CL500 <- CL300)