Specifications
3 – Configuration Tutorial
42 R400
5
Click the Sample Interval field and select an interval from the list. (for
example, 5 seconds)
6
In the first Point ID field, enter PUMPSTS (the point ID of the status point
you created in 3.4.1 “Defining a Status Point to Control a Pump”).
You can enter the point ID using the Point Browser. Click the Point Browser
button to call up the Point Browser. Select the required point ID and click
Apply. The point ID is automatically entered into the Point ID field.
7
In the second Point ID field, enter TANKLEVEL (the point ID of the analog
point you created in 3.4.2 “Defining an Analog Point to Monitor the Level of
a Tank”).
8
From the Parameter list select the parameter you want to trend for each
point.
9
To display the trace for each point, ensure that Pen on is enabled for each
point. (The Pen on/off checkbox should be enabled by default, if not, click
the checkbox to enable it.)
10
Select the View Trend link to display the trend.
Note If the MNGR or ENGR security level required to change traces
checkbox is selected, the points you choose can only be changed by a user
with mngr or engr security level.
Figure 3.25 Trend Set Configuration Display
plscpcg.book Page 42 Monday, May 28, 2001 10:11 AM