Specifications
Troubleshooting Station Connections and Station Displays
PlantScape Server and Client Configuration Guide 533
When Station Cannot Find Display Files
If Station connects successfully but cannot call up a display, it generally responds
with the message:
The display file xxx was not found.
To resolve this problem you need to:
• Check the registry entry for the path for Station displays. See “PlantScape
Control Panel” on page 505 for information on using the PlantScape
Control Panel utility to set or check the registry entry for display paths.
• Check the display paths specified in the Station setup file. For details, see
“Displays Tab” on page 70.
Alphanumeric Display Object in Error
If an alphanumeric display object does not show an expected value but instead
shows a series of red question marks (??????????), this indicates the server is unable
to determine a value. Check the configuration of the display object for any errors.
A Point History display might show a series of question marks (??????????). This
indicates a value of minus zero.