13 – Configuring Reports
284 R400
(For a list of standard point parameters, see “Summary of Point Parameters
and Addresses” on page 133.)
Print_Format
“FORTRAN” style format descriptors:
When accessing status points, the PV or OP can be expressed as a state descriptor
by specifying the print format as:
Sn State descriptor of length n characters.
[History Type]
Can be one of:
EULO 0% Range xx
EUHI 100% Range xx
Parameter ANA STA ACC
In Integer
Zn Short integer in hexadecimal notation
Fn.m Floating point
En.m Floating point in exponential form
An ASCII
D Date (DD-MMM-YY) integer date is in minutes
T Time (HH:MM:SS) real data is in seconds
where:
n Is the width of the field and m is the number of decimal places.
H1M History Standard 1 minute snapshot
H6M History Standard 6 minute snapshot
H1H History Standard 1 hour average